TRAVIS AFB, CA —
OSHA Inspection: U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON in 411 AIRMAN DRIVE, TRAVIS AFB, CA 94535 (NAICS 928110). OSHA activity number 339675027.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. AIR FORCE 60TH CIVIL ENGINEERING SQUADRON
- Site address
- 411 AIRMAN DRIVE
- City
- TRAVIS AFB
- State
- CA
- ZIP
- 94535
- Mailing
- 540 AIRLIFT DRIVE BLDG. 381, WING 2-C, TRAVIS AFB, CA 94535
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 50
- Ownership type
- D
Citations
2 citations on file for this inspection.
1910.147 C06 I C
- Issued
- Sep 19, 2014
- Abate by
- Oct 16, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i)(C): Where lockout was used for energy control, the periodic inspection did not include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected: HVAC: Employees authorized to perform lock out procedures were not annually evaluated on machine specific procedures for multi-energy source equipment such as air compressors, which have both electric and pneumatic energy.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Sep 19, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Bldg. 874 Structures Shop: Two disconnects on the back wall which energized the sawdust extraction system and the oscillating spindle system had no markings which indicated their purpose. The U.S. Air Force 60th Civil Engineering Squadron was previously cited for a violation of this occupational safety and health standard 1910.303(f)(2), which was contained in OSHA inspection number 191646, citation number 01, item number 004 and was affirmed as a final order on 08/22/2012, with respect to a workplace located at 241 V Street Travis AFB, CA 94535.
Recent events (1)
- — Z (R) $0
More inspections at U.S. AIR Force 60TH Civil Engineering Squadron
View U.S. AIR Force 60TH Civil Engineering Squadron's full OSHA safety record →