Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VA MEDICAL CENTER-JESSE BROWN

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of VA MEDICAL CENTER-JESSE BROWN in 820 S. DAMEN AVENUE, CHICAGO, IL 60612 (NAICS 622110). OSHA activity number 332425180.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch VA Medical Center-Jesse Brown — free Get an email when a new federal OSHA severe-injury report for VA Medical Center-Jesse Brown is published. One employer, no account, unsubscribe in one click.
Site address
820 S. DAMEN AVENUE
City
CHICAGO
State
IL
ZIP
60612
Mailing
820 S. DAMEN AVENUE, CHICAGO, IL 60612
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
1800
Ownership type
D

7 citations on file for this inspection.

1910.147 C06 II

Serious Gravity 1 55 exposed
Issued
Aug 17, 2012
Abate by
Dec 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed:    a) VA Medical Center Jesse Brown- On or about 02/24/12, the employer did not certify that periodic inspections of the company's energy control procedures for employees authorized to lockout had been conducted. Employees were exposed to the hazards of uncontrolled energy sources.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.23 E02

Repeat Gravity 1 1 exposed
Issued
Aug 17, 2012
Abate by
Dec 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.23(e)(2):     The stair railing was less than 30 inches from upper surface of top rail to surface of tread in line with face of riser at forward edge of tread:    a) Taylor Building Basement- On or about 02/24/12, employees were required to use stair railings that were below   (15 inches) the minimum vertical height of 30 inches. Employees were exposed to a fall hazard.    b) Ogden Building Basement- On or about 02/24/12, employees were required to use stair railings that were below   (15 inches) the minimum vertical height of 30 inches. Employees were exposed to a fall hazard.    c) Damen Penthouse Near Entrance- On or about 02/24/12, employees were required to use stair railings that were below (15 inches) the minimum vertical height of 30 inches. Employees were exposed to a fall hazard.    d) Damen Penthouse Center High Stairs- On or about 02/24/12, employees were required to use stair railings that were below (15 inches) the minimum vertical height of 30 inches. Employees were exposed to a fall hazard.    e) Damen Penthouse Back Near Pit- On or about 02/24/12, employees were required to use stair railings that were below (15 inches) the minimum vertical height of 30 inches. Employees were exposed to a fall hazard.    The VA was previously cited for a serious violation of the Occupational Safety and Health standard or its eqivalent standard 29 CFR 1910.23(e)(2), which was contained in OSHA inspection number 314814724, Citation Number 01, Item 4a, Issued or final order on May 18, 2011 respect to a workplace at 3001 Green Bay Road, North Chicago, Illinois.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

1910.24 H

Repeat Gravity 1 1 exposed
Issued
Aug 17, 2012
Abate by
Dec 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.24(h):     Standard railings were not provided on the open sides of all exposed stairways and stair platforms:      a) Damen Penthouse Near Entrance- On or about 02/24/12, employees were required to use a flight of stairs with one open side and a railing that was below (15 inches) the minimum vertical height of 30 inches. Employees were exposed to a fall hazard.    b) Damen Penthouse Back Near Pit- On or about 02/24/12, employees were required to use a flight of stairs with one open side and a railing that was below (15 inches) the minimum vertical height of 30 inches. Employees were exposed to a fall hazard.    The VA was previously cited for a serious violation of the Occupational Safety and Health standard or its equivalent standard 29 CFR 1910.24(h), which was contained in OSHA inspection number 314814724, Citation Number 01, Item 4b, and was affirmed as a final order on May 18, 2011 with respect to a workplace at 3001 Green Bay Road, North Chicago, Illinois.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

1910.146 C01

Repeat 55 exposed
Issued
Aug 17, 2012
Abate by
Dec 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.146(c)(1):     The employer did not evaluate the workplace to determine if any spaces were permit-required confined spaces:    a) VA Medical Center-Jesse Brown- On or about 02/24/12, the employer had not conducted the required evaluation of the workplace to identify confined spaces.    The Veterans Administration was previously cited for a violation of this Occupational Safety and Health standard or its equivalent standard 29CFR 1910.146(c)(1), which was contained in OSHA inspection number 313175937, Citation Number 01, Item 6a, and was affirmed as a final order on June 02, 2010 with respect to a workplace at One Veterans Drive, Minneapolis, Minnesota.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

1910.332 B01

Repeat Gravity 5 55 exposed
Issued
Aug 17, 2012
Abate by
Dec 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1):     Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    a) VA Medical Center-Jesse Brown- On or about 02/24/12, maintenance employees (Electrical, HVAC) assigned to trouble shoot and test energized electrical parts such as but not limited to, voltage testing above 50 volts, were not provided training in electrical safety-related work practices, thereby exposing the employees to the hazards of electrical shock, electrocution and arc flash/blast.    The VA was previously cited for a serious violation of the Occupational Safety and Health standard or its equivalent standard 29 CFR 1910.332(b)(1), which was contained in OSHA inspection number 313939928, Citation Number 01, Item 4a, Issued or final order on December 22, 2010 respect to a workplace at 5000 5th Avenue, Hines, Illinois.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

1910.335 A01 I

Repeat Gravity 5 55 exposed
Issued
Aug 17, 2012
Abate by
Dec 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i):     Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    a) VA Medical Center-Jesse Brown- On or about 2/24/12, maintenance employees working in areas where there were potential electrical were not provided the necessary electrical protective equipment to protect them from electrical shock, electrocution and arc flash/blast.    The VA was previously cited for a serious violation of the Occupational Safety and Health standard or its equivalent standard 29 CFR 1910.335(a)(1)(i), which was contained in OSHA inspection number 314814724, Citation Number 01, Item 5, Issued or final order on December 22, 2010 respect to a workplace at 5000 5th Avenue, Hines, Illinois.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

1910.1001 J03 V

Repeat 25 exposed
Issued
Aug 17, 2012
Abate by
Sep 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1001(j)(3)(v): The building or facility owner did not post, at the entrance to a mechanical rooms or areas in which employees reasonably could be expected to enter and which contained ACM and/or PACM, a sign which identified the material which is present, its location and the appropriate work practices:    a) Damen Building Penthouse- On or about 02/24/12, the employer did not post signs at entrances to mechanical rooms/areas where employees reasonably can be expected to enter and which contain ACM and or PACM.    The VA was previously cited for a serious violation of the Occupational Safety and Health standard or its equivalent standard 29 CFR 1910.1001(j)(3)(v), which was contained in OSHA inspection number 314965054, Citation Number 01, Item 1, and was affirmed as a final order on June 15, 2011 respect to a workplace at 3001 Green Bay Road, North Chicago, Illinois.
Recent events (2)
  • — I (R) $0
  • — Z (R) $0

View VA Medical Center-Jesse Brown's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332425180.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.