Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SS-ART & ENGRAVING CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SS-ART & ENGRAVING CORP. in 1023 COMMERCE AVE., UNION, NJ 07083 (NAICS 323122). OSHA activity number 332428580.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ss-Art & Engraving Corp. — free Get an email when a new federal OSHA severe-injury report for Ss-Art & Engraving Corp. is published. One employer, no account, unsubscribe in one click.
Site address
1023 COMMERCE AVE.
City
UNION
State
NJ
ZIP
07083
Mailing
1023 COMMERCE AVE., UNION, NJ 07083
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323122
Employees
8
Ownership type
A

9 citations on file for this inspection.

1910.106 D05 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 13, 2012
Abate by
Jul 30, 2012
Penalty
Initial $2,550 · Current $1,657 Reduced
29 CFR 1910.106(d)(5)(i):  Flammable or combustible liquids were not stored so as to limit safe egress of employees:    a/ SS Art/Union NJ Site - Plant Chemical Storage Shed Area:  Class 1B flammable liquids (Flash Point below 100 deg.F) were not adequately stored in their designated locations in the Shed to prevent a fire hazard and safe agress from the Shed by employees.    Observed on/or about 2/29/2012.
Recent events (2)
  • — I (S) $1657
  • — Z (S) $2550

1910.106 E06 II

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 13, 2012
Abate by
Jul 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(ii):   Class I liquids were  dispensed into containers without the nozzle and container electrically interconnected:    a/ SS Art/Union NJ Site - Plant Chemical Storage Shed Area: Class 1B flammable liquids (Fllash Point below 100 Deg.F) are dispensed without bonding and grounding. Flammable liquids include but not limited to Alcohol, Acetone, etc.      Observed on/or about 2/29/2012.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 F06

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 13, 2012
Abate by
Jul 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.106(f)(6):  "No Smoking" signs were not conspicouslly posted where hazards from flammable liquids were normally present:    a/ SS Art/Union NJ Site - Plant Chemical Storage Shed Area:  A "No Smoking" sign is not provided where Class 1B flammable liquids (Fllash Point below 100 Deg.F) are stored and dispensed.  Flammable liquids include but  not limited to Alcohol, Acetone, etc.       Observed on/or about 2/29/2012.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E06 I

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 13, 2012
Abate by
Jul 30, 2012
Penalty
Initial $3,060 · Current $1,990 Reduced
29 CFR 1910.106(e)(6)(i):  Adequate precautions were not taken to prevent the ignition of flammable vapors:    a/ SS Art/Union NJ Site - Plant Plate Making Area/Plate Wash Room :   A non-classified electric metall framed portable drop light was used to view a plate washing operation where Alcohol (Class 1B Flammable Liquid - Flash Point below 100 Deg.F) was used as the washing agent. The metal frame of the drop light became hot, igniting the Alcohol vapors.      Observed on/or about 2/29/2012.
Recent events (2)
  • — I (S) $1990
  • — Z (S) $3060

1910.157 G01

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 13, 2012
Abate by
Aug 3, 2012
Penalty
Initial $1,530 · Current $994 Reduced
29 CFR 1910.157(g)(1):   An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:    a/ SS Art/Union NJ Site - Plant Area:  Employees who are allowed to and/or designated to fight a minor fire in the event of a fire emergency were not provided initial training and at least annually thereafter.    Observed on/or about 2/29/2012.
Recent events (2)
  • — I (S) $994
  • — Z (S) $1530

1910.307 C

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 13, 2012
Abate by
Aug 3, 2012
Penalty
Initial $3,060 · Current $1,990 Reduced
29 CFR 1910.307(c):   Equipment, wiring methods, and installations of equipment in hazardous  Class 1 Division I locations were not intrinsically safe, approved for the hazardous Class 1 Division I location, or safe for the hazardous Class 1 Division I location:    a/ SS Art/Union NJ Site/Plant Plate Making Area - Plate Wash Room:    1/  A non-classified electric metall framed portable drop light was used to view a plate washing/cleaning operation where Alcohol (Class 1B Flammable Liquid - Flash Point below 100 Deg.F) was used as the washing agent.    2/  The electric metal framed portable drop light was plugged into a non-classified 2 receptacle outlet that was located on the wall outside of the Plate Wash Room adjacent to the Plate Wash Room door.     Class 1 Division 1 and 11 electrical outlet(s) and portable electric equipment that were used within 25 ft. of a Class 1 Division 1 and 11 location (and/or other approved means) were not provided.    Observed on/or about 2/29/2012.
Recent events (2)
  • — I (S) $1990
  • — Z (S) $3060

1910.1200 F05

Serious Gravity 1 4 instances 6 exposed
Issued
Jul 13, 2012
Abate by
Jul 30, 2012
Penalty
Initial $1,530 · Current $994 Reduced
29 CFR 1910.1200(f)(5):   The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged, or marked with the identity the hazardous chemical(s) contained therein:      a/ SS Art/Union NJ Site - Plant Production Areas:  Secondary containers of chemicals that could include the mixture of corrosives/water and/or flammables/water were not marked. Chemicals on site include but not limited to XL Developer, Cronite, Alcohol, Acetone, Soda Ash, Nitric Acid, etc.          Observed on/or about 2/29/2012.
Recent events (2)
  • — I (S) $994
  • — Z (S) $1530

1910.37 B02

Other-than-serious 1 instance 2 exposed
Issued
Jul 13, 2012
Abate by
Jul 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):  Each exit was not clearly visible and marked by a sign reading "Exit":      a/ SS Art/Union NJ Site - Plant Plate Wash Room:  The designated exit door was not provided with an "exit" sign.    Observed on/or about 2/29/2012.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.132 D01

Other-than-serious 1 instance 8 exposed
Issued
Jul 13, 2012
Abate by
Aug 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(1):   The employer did not assess the workplace to determine if hazards were present, or were likely to be present, which necessitated the use of personal protective equipment:    a/ SS Art/Union NJ Site - Plant Area:  The employer had not done a hazard assessment to ensure that employees who are required to use and/or handle chemicals in the workplace were provided with the proper personal protectors.  Chemicals include but not limited to Nitric/Sulfuric Acids, Soda Ash, XL Developer, etc.    Observed on/or about 2/29/2012.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Ss-Art & Engraving Corp.'s full OSHA safety record →