Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE LONGABERGER COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of THE LONGABERGER COMPANY in 5363 RAIDERS RD., FRAZEYSBURG, OH 43822 (NAICS 321920). OSHA activity number 332430081.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Longaberger Company — free Get an email when a new federal OSHA severe-injury report for The Longaberger Company is published. One employer, no account, unsubscribe in one click.
Site address
5363 RAIDERS RD.
City
FRAZEYSBURG
State
OH
ZIP
43822
Mailing
1500 EAST MAIN ST., NEWARK, OH 43822
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321920
Employees
500
Ownership type
A

2 citations on file for this inspection.

1910.333 A

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 20, 2012
Abate by
Oct 9, 2012
Penalty
Initial $3,750 · Current $2,250 Reduced
29 CFR 1910.333(a):     "General." Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized.The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards.    a. At the workplace, for employees who routinely perform work on or near energized parts (480 VAC) such as testing, troubleshooting, voltage measuring, and other tasks in and around the electrical panel box for the dust collector, neither a flash hazard analysis was conducted to determine the proper protection required nor was a flash protection boundary established to protect employees from shock, arc flash, or arc blast.     ABATEMENT NOTE: One method of abatement, among others, includes conducting a flash hazard analysis in compliance with NFPA 70E Standard for Electrical Safety in the Workplace to determine the flash protection boundary and the use of electrical protective equipment as necessary for the specific related hazards of each task.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $3750

1910.137 B02 VIII

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 20, 2012
Abate by
Apr 19, 2012
Penalty
Initial $3,750 · Current $2,250 Reduced
29 CFR 1910.137(b)(2)(viii):     Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-5 and Table I-6.    a. At the workplace, the employer did not ensure that periodic electrical tests were completed on the electrical protective gloves used by maintenance employees.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $3750

View The Longaberger Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332430081.