OSHA Inspection: AIR FORCE RESEARCH LABORATORY

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of AIR FORCE RESEARCH LABORATORY in BLDG. 8451 10 E. SATURN BLVD., EDWARDS AFB, CA 93524 (NAICS 488190). OSHA activity number 332801182.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AIR Force Research Laboratory for free Get an email when a new federal OSHA severe-injury report for AIR Force Research Laboratory is published. One employer, no account, unsubscribe in one click.
Site address
BLDG. 8451 10 E. SATURN BLVD.
City
EDWARDS AFB
State
CA
ZIP
93524
Mailing
95 ABW/CE 225 NORTH ROSAMOND BLVD., EDWARDS AFB, CA 93524
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
20
Ownership type
Federal government (D)

5 citations on file for this inspection.

1910.165 B02

Serious Gravity 5 1 instance 12 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.165(b)(2): The employee alarm could not be perceived above ambient noise or light levels by all employees in the affected portions of the workplace:    a) At test cells - On or about 3/8/12, the employee alarm could not be heard by employees wearing double hearing protection.
Recent events (1)
  • · Z (S) $0

1910.303 B01

Serious Gravity 5 1 instance 6 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:    a) At Room 71, Lab hood 8451-71J - On or about 3/7/12, a stirrer/hotplate's flexible cord insulation was damaged by solvents.
Recent events (1)
  • · Z (S) $0

1910.303 B07 I

Serious Gravity 5 2 instances 2 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:    a) In Room 64, behind desk - On or about 3/7/12, an electrical junction box had open knockouts.    b) In Room 18, adjacent to door of EC-1 - On or about 3/8/12, an electrical box had open knockouts.
Recent events (1)
  • · Z (S) $0

1910.303 G01

Serious Gravity 5 2 instances 12 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    a) At Room 24 - On or about 3/8/12, an electrical panel was blocked by laboratory equipment.    b) At Room 24 - On or about 3/8/12, an electrical panel was blocked by a liquid nitrogen tank.
Recent events (1)
  • · Z (S) $0

1910.305 J02 IV

Serious Gravity 5 10 instances 6 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:    a) At Room 71, Lab hood 8451-71B - On or about 3/7/12, 115V electrical outlets below the lab hood had no GFCI protection.     b) At Room 71, Lab hood 8451-71C - On or about 3/7/12, 115V electrical outlets below the lab hood had no GFCI protection.     c) At Room 71, Lab hood 8451-71D - On or about 3/7/12, 115V electrical outlets below the lab hood had no GFCI protection.     d) At Room 71, Lab hood 8451-71G - On or about 3/7/12, 115V electrical outlets below the lab hood had no GFCI protection.    e) At Room 71, Lab hood 8451-71H - On or about 3/7/12, 115V electrical outlets below the lab hood had no GFCI protection.    f) At Room 71, Lab hood 8451-71I - On or about 3/7/12, 115V electrical outlets below the lab hood had no GFCI protection.    g) At Room 71, Lab hood 8451-71J - On or about 3/7/12, 115V electrical outlets below the lab hood had no GFCI protection.    h) At Room 67, Lab hood 8451-67A - On or about 3/7/12, 115V electrical adjacent to the lab hood had no GFCI protection.    i) At Room 67, Lab hood 8451-67B - On or about 3/7/12, 115V electrical adjacent to the lab hood had no GFCI protection.    j) At Room 83, Lab hood 8451-83C - On or about 3/8/12, 115V electrical adjacent to the lab hood had no GFCI protection.