Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: AIR FORCE RESEARCH LABORATORY

Unprogrammed Related inspection · Health discipline

On , OSHA opened an unprogrammed Related health inspection of AIR FORCE RESEARCH LABORATORY in BLDG. 8451 10 E. SATURN BLVD., EDWARDS AFB, CA 93524 (NAICS 488190). OSHA activity number 332802206.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AIR Force Research Laboratory for free Get an email when a new federal OSHA severe-injury report for AIR Force Research Laboratory is published. One employer, no account, unsubscribe in one click.
Site address
BLDG. 8451 10 E. SATURN BLVD.
City
EDWARDS AFB
State
CA
ZIP
93524
Mailing
95 ABW/CE 225 NORTH ROSAMOND BLVD., EDWARDS AFB, CA 93524
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
15
Ownership type
Federal government (D)

5 citations on file for this inspection.

1910.106 D04 IV

Serious 2 instances 12 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(4)(iv): An inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system that was designed to provide for a complete change of air within the room at least six times per hour:    a) In Room 60 - On or about 3/7/12, the exhaust ventilation for the flammable storage room was capped in the penthouse.    b) In Room 80 - On or about 3/7/12, the exhaust ventilation for the flammable storage room was non-functional.
Recent events (1)
  • · Z (S) $0

1910.141 A05

Serious Gravity 5 1 instance 12 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.141(a)(5): Enclosed workplaces were not so constructed, equipped, and maintained as to prevent the entrance or harborage of rodents, insects, or other vermin:    a) Access areas above Rooms 71, 64, 91, and 67 - On or about 6/21/12, the workplace was not maintained to prevent the entrance or harborage of rodents.
Recent events (1)
  • · Z (S) $0

1910.1200 F09

Serious Gravity 1 1 instance 1 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(9): The employer did not ensure that labels or other forms of warning were legible, in English, and prominently displayed on the container, or readily available in the work area throughout each work shift:    a) In Room 24 - On or about 3/8/2012, a bottle of Fomblin oil did not have an identifying label that was legible.
Recent events (1)
  • · Z (S) $0

1910.1450 E03 III

Serious Gravity 5 4 instances 5 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1450(e)(3)(iii): The employer's Chemical Hygiene Plan did not include a requirement that fume hoods and other protective equipment functioned properly and/or did not include specific measures that would be taken to ensure proper and adequate performance of such equipment:    a) In Room 71, Lab hood 8451-71B - On or about 3/7/12, the laboratory hood did not have an average face velocity of at least 80 fpm.     b) In Room 67- On or about 3/7/12, room air was not balanced so as to prevent attic air re-entrainment.    c) On the Roof, - On or about 6/21/12, the discharge stacks exhaust number 408-72 and 408-73 were not at least 10 feet above the highest roof level.      d) At Bldg. 8451 - On or about 3/7/12, an air balancing study was not performed following installation of new air handling units to ensure that the hoods and the ventilation system were functioning correctly.
Recent events (1)
  • · Z (S) $0

1910.1001 J03 V

Other-than-serious 1 instance 5 exposed
Issued
Aug 31, 2012
Abate by
Sep 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1001(j)(3)(v): The building or facility owner did not post, at the entrance to a mechanical room or area in which employees reasonably could be expected to enter and which contained ACM and/or PACM, a sign which identified the material which is present, its location and the appropriate work practices:    a) In the Penthouse - On or about 3/7/12, the building owner did not post a sign at the entrance to the area which identified the material was present, its location and the appropriate work practices.
Recent events (1)
  • · Z (O) $0

View AIR Force Research Laboratory's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 332802206.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.