SAN DIEGO, CA —
OSHA Inspection: NAVY EXCHANGE SERVICE COMMAND
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NAVY EXCHANGE SERVICE COMMAND in 2260 CALLAGAN HIGHWAY BLDG. 3187A, 3379, 3155, SAN DIEGO, CA 92136 (NAICS 452111). OSHA activity number 332811462.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NAVY EXCHANGE SERVICE COMMAND
- Site address
- 2260 CALLAGAN HIGHWAY BLDG. 3187A, 3379, 3155
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92136
- Mailing
- 2260 CALLAGAN HIGHWAY BLDG. 3187A, SAN DIEGO, CA 92136
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 452111
- Employees
- 200
- Ownership type
- D
Citations
10 citations on file for this inspection.
1910.303 B02
- Issued
- Apr 24, 2012
- Abate by
- Apr 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: 8th Street Will Call, Ezekiel's Work Area: On March 9, 2012, and at times prior thereto, a power tap had been tied to a steel beam and used to permanently energize extension cords.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Apr 24, 2012
- Abate by
- Apr 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used for purposes prohibited by subparagraphs (a) through (f) of this section: 8th Street Will Call, Ezekiel's Work Area: On March 9, 2012, and at times prior thereto, three extensions cords were used in lieu of permanent wiring.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Apr 24, 2012
- Abate by
- Apr 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords were used and run through holes in walls, ceilings, or floors: 8th Street Will Call: On March 9, 2012, and at times prior thereto, a spliced white extension cord was run through a hole in the wall separating the main work area and Ezekiel's work area.
Recent events (1)
- — Z (S) $0
1910.305 G02 II
- Issued
- Apr 24, 2012
- Abate by
- Apr 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were used were in continuous lengths with a splice or tap: 8th Street Will Call: On March 9, 2012, and at times prior thereto, a white extension cord had been spliced together and the inner conductors were exposed along the wall in the main work area.
Recent events (1)
- — Z (S) $0
1910.305 B02
- Issued
- Apr 24, 2012
- Abate by
- Apr 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: 8th Street Will Call/FISC Wall: An junction box inches from the ground, next to an exit, was not provided with a cover and the live inner conductors were exposed.
Recent events (1)
- — Z (S) $0
1910.332 B01
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety related work practices required by 29 CFR 1910.331 through 1910.335 that pertained to their respective job assignments: On March 9, 2012,nd at times prior thereto, the electrician had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live electrical work, live trouble-shooting and verifying whether or not electrical equipment was properly de-energized.
Recent events (1)
- — Z (S) $0
1910.333 A01
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee worked on or near them: On March 9, 2012,and at times prior thereto, the employer allowed live work including but not limited to live cable installation.
Recent events (1)
- — Z (S) $0
1910.333 A02
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(2): Where exposed live parts where not de-energized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved: On March 9, 2012,and at times prior thereto, the employer had not developed and implemented an Electrical Safety Related Work Practices Program to adress hazards caused by arc flash, arc blast and electric shock in the facility. Employees conducted live cables installations and ballast chages, live trouble-shooting and tested electrical equipment to ensure that it was properly de-energized.
Recent events (1)
- — Z (S) $0
1910.335 A01 II
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(ii): Employees working in areas where there were potential electrical hazards were not provided with and/or did not use, electrical personal protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: On March 9, 2012,and at times prior thereto, personal protective equipment such as, but not limited to, voltage rated gloves, FR clothing, and face shields were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized.
Recent events (1)
- — Z (S) $0
1910.335 A02 I
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(i): :When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have contact with such conductors or parts: On March 9, 2012,and at times prior thereto, voltage rated tools were not provided to electrician personnel when working near energized electrical equipment.
Recent events (1)
- — Z (S) $0
More inspections at Navy Exchange Service Command
View Navy Exchange Service Command's full OSHA safety record →
More inspections in this industry (NAICS 452111)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332811462.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.