MIDDLETOWN, OH —
OSHA Inspection: MIDDLETOWN TUBE WORKS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MIDDLETOWN TUBE WORKS, INC. in 2201 TRINE ST., MIDDLETOWN, OH 45044 (NAICS 331111). OSHA activity number 332828144.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MIDDLETOWN TUBE WORKS, INC.
- Site address
- 2201 TRINE ST.
- City
- MIDDLETOWN
- State
- OH
- ZIP
- 45044
- Mailing
- 2201 TRINE ST., MIDDLETOWN, OH 45044
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331111
- Employees
- 87
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C06 I C
- Issued
- Jun 21, 2012
- Abate by
- Jul 20, 2012
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.147(c)(6)(i)(C): Where lockout is used for energy control, the periodic inspection shall include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected. Periodic inspections of the company's specific energy control procedures were inadequate in that they did not include a review with each authorized employee of the specific energy control procedures developed by the company.
Recent events (2)
- — I (S) $3500
- — Z (S) $3500
1910.147 C07 I B
- Issued
- Jun 21, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $2,100 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i)(B): Each affected employee shall be instructed in the purpose and use of the energy control procedure. Temporary employees working at the Company had not been instructed on the purpose and use of the energy control procedure.
Recent events (2)
- — I (S) $0
- — Z (S) $2100
1910.178 L03
- Issued
- Jun 21, 2012
- Abate by
- Aug 3, 2012
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.178(l)(3): Training program content. Powered industrial truck operators shall receive initial training in the following topics, except in topics which the employer can demonstrate are not applicable to safe operation of the truck in the employer's workplace. Employees who operate the Raymond Side Loader powered industrial truck had not received initial formal instruction on truck-related and workplace-related topics.
Recent events (2)
- — I (O) $1400
- — Z (S) $2800
1910.332 B01
- Issued
- Jun 21, 2012
- Abate by
- Feb 1, 2013
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.332(b)(1): Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments. Employees who perform energized electrical work on 110 Volts AC to 480 Volts AC consisting of troubleshooting, voltage testing involving the use of a multi-meter and amperes using an amp probe had not received training on what and when to use personal protective equipment to protect themselves against electric shock and arc flash.
Recent events (2)
- — I (S) $3500
- — Z (S) $3500
1910.335 A01 I
- Issued
- Jun 21, 2012
- Abate by
- Aug 3, 2012
- Penalty
- Initial $3,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with,and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.Note: Personal protective equipment requirements are contained in subpart I of this part. Employees who were performing energized electrical work in the form of voltage testing on 480 Volts AC and below were not provided with the appropriate FR clothing to protect themselves against arc flash.
Recent events (2)
- — I (S) $0
- — Z (S) $3500
1910.212 A03 II
- Issued
- Jun 21, 2012
- Penalty
- Initial $7,000 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): The point of operation of machines whose operation exposes an employee to injury, shall be guarded. The guarding device shall be in conformity with any appropriate standards therefor, or, in the absence of applicable specific standards, shall be so designed and constructed as to prevent the operator from having any part of his body in the danger zone during the operating cycle. On or about March 12, 2012, in the Rework Area, an employee was exposed to a amputation hazard while using a Cold Saw Machine with an inadequate point of operation guard to saw 1/2 inch square metal tubing bundles. Middletown Tube Works, Inc. was previously cited for a violation of the occupational safety and health standard or its equivalent standard, which was contained in OSHA inspection number 314100280, citation 1, item 1, which was affirmed as a final order on March 8, 2010, with respect to a workplace located at 2201 Trine Street, Middletown, OH 45044
Recent events (2)
- — I (S) $3000
- — Z (R) $7000
1910.305 G02 III
- Issued
- Jun 21, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $4,200 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. In the Maintenance Area, an employee was exposed to a electric shock hazard from the flexible cord on the Miller Portable Arc Welding uint pulled away from the fitting on the 220 Volt AC electrical disconnect switchbox, creating strain on the terminal screws. Middletown Tube Works, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard, which was contained in OSHA inspection number 314100280, citation 1, item 5, which was affirmed as a final order on March 8,2010, with respect to a workplace located at 2201 Trine Street, Middletown, OH 45044.
Recent events (2)
- — I (S) $2000
- — Z (R) $4200
1910.137 B02 VIII
- Issued
- Jun 21, 2012
- Abate by
- Jul 20, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-5 and Table I-6. Employees performing energized electrical work were wearing insulated rubber gloves which had not tested in accordance with Table I-6.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Middletown Tube Works, INC.
View Middletown Tube Works, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 331111)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332828144.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.