Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: ABC/FRY-WAGNER, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ABC/FRY-WAGNER, INC. in 15850 SANTA FE TRAIL DRIVE, LENEXA, KS 66219 (NAICS 484210). OSHA activity number 332833656.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Abc/Fry-Wagner, INC. for free Get an email when a new federal OSHA severe-injury report for Abc/Fry-Wagner, INC. is published. One employer, no account, unsubscribe in one click.
Site address
15850 SANTA FE TRAIL DRIVE
City
LENEXA
State
KS
ZIP
66219
Mailing
15850 SANTA FE TRAIL DRIVE, LENEXA, KS 66219
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
484210
Employees
130
Ownership type
Private (A)

8 citations on file for this inspection.

5(a)(1)

Serious 5 instances 10 exposed
Issued
Apr 30, 2012
Abate by
Jun 12, 2012
Penalty
Initial $3,443 · Current $1,721 Reduced
OSH ACT of 1970 Section (5)(a)(1):     The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employee(s) were exposed to a crushing hazard:    (a)  At the facility employee(s) working / walking along the Packing Bay in warehouse 1 where steel storage racks had not been periodically inspected for corrosion, structural damage, or overloading.  Column leg 2 on the west wall was severely bent with pallets of materials still in the storage racks, thus exposing employee(s) to physical injuries.    (b)  At the facility employee(s) working / walking along the Packing Bay in warehouse 1 where steel storage racks had not been periodically inspected for corrosion, structural damage, or overloading.  Column leg 3 on the east wall was severely bent with pallets of materials still in the storage racks, thus exposing employee(s) to physical injuries.    (c)  At the facility employee(s) working / walking along the Packing Bay in warehouse 1 where steel storage racks had not been periodically inspected for corrosion, structural damage, or overloading.  Column leg 7 on the east wall had the bracing support severely bent with pallets of materials still in the storage racks, thus exposing employee(s) to physical injuries.    (d)  At the facility employee(s) working / walking along in warehouse 2, row 1, column leg 6 (rack identification number - 20119) where steel storage racks had not been periodically inspected for corrosion, structural damage, or overloading.  Column leg 6 was severely bent with pallets of materials still in the storage racks, thus exposing employee(s) to physical injuries.    (e)  At the facility employee(s) working / walking along in warehouse 2, row 2, column leg 6 (rack identification number - 1545) where steel storage racks had not been periodically inspected for corrosion, structural damage, or overloading.  Column leg 6 was severely bent with pallets of materials still in the storage racks, thus exposing employee(s) to physical injuries.    Among other methods, one feasible and acceptable method to correct this hazard is:  Develop and implement a structural integrity program to periodically inspect storage racks as recommended by the Rack Manufacturing Instutite Specification for the Design, Testing, and Utilization of Industrial Steel Storage Racks 1997 Edition, section 1.4.1.    29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violations have been completed.
Recent events (2)
  • · I (S) $1721.25
  • · Z (S) $3442.5

1910.303 B02

Other-than-serious 1 instance 5 exposed
Issued
Apr 30, 2012
Abate by
Jun 12, 2012
Penalty
Initial $2,754 · Current $1,377 Reduced
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    Employee(s) operating the electrical switch for the furnace on the mezzanine in warehouse 1 were exposed to electrical hazards due to the electrical switch for the furnace not being mounted to a surface as required by the U.L. listing instructions.     29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Recent events (2)
  • · I (O) $1377
  • · Z (S) $2754

1910.305 B01 II

Other-than-serious 1 instance 5 exposed
Issued
Apr 30, 2012
Abate by
Jun 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii):  Unused openings in boxes, cabinets, or fittings were not effectively closed:    Employee(s) using the electrical switch for the furnace in warehouse 1 (mezzanine) were exposed to electrical hazards due to unused opening on the right and bottom side of the furnace's electrical switch not being closed.    29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Recent events (2)
  • · I (O) $0
  • · Z (S) $0

1910.304 G05

Other-than-serious 2 instances 10 exposed
Issued
Apr 30, 2012
Abate by
May 1, 2012
Penalty
Initial $2,754 · Current $1,377 Reduced
29 CFR 1910.304(g)(5):     The paths to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective:    Employee(s) using the dock lights in warehouse 2 between dock doors 5 & 6 and 8 & 9 were exposed to electrical hazard due to no grounding pin on the plug end of the dock light power cord.    29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Recent events (2)
  • · I (O) $1377
  • · Z (S) $2754

1910.303 G02 I

Serious Gravity 5 3 instances 10 exposed
Issued
Apr 30, 2012
Abate by
Jun 12, 2012
Penalty
Initial $3,443 · Current $1,721 Reduced
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    (a)  Employee(s) working / walking around a column post north of dock doors 8 & 9 in warehouse 2 were exposed to electrical hazards due to a damaged receptacle box exposing live conductors.    (b)  Employee(s) working / walking around the south wall of record storage in warehouse 2 were exposed to electrical hazards due to 1-1/2 inch of live wiring exiting from conduit, not being guarded.    (c)  Employee(s) operating the Campbell Hausfeld compressor were exposed to electrical hazards due to 6 - 7 inches of the flexible conduit unraveling, thus exposing live conductors.     29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Recent events (2)
  • · I (S) $1721.25
  • · Z (S) $3442.5

1910.305 G02 III

Other-than-serious 1 instance 1 exposed
Issued
Apr 30, 2012
Abate by
Jun 12, 2012
Penalty
Initial $2,066 · Current $1,033 Reduced
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    Employee(s) operating the Campbell Hausfeld compressor were exposed to electrical hazards due to no strain relief being provided for the flexible conduit exiting the junction box, thus exposing live conductors.     29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Recent events (2)
  • · I (O) $1032.75
  • · Z (S) $2065.5

1910.1200 H

Other-than-serious 1 instance 10 exposed
Issued
Apr 30, 2012
Abate by
May 29, 2012
Penalty
Initial $2,066 · Current $1,033 Reduced
29 CFR 1910.1200(h):     Employees were not provided effective information and training as specified in 29 CFR 1910.1200(h)(1) and -2 on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard was introduced at the establishment:    At the establishment employee(s) working with hazardous chemical products such as propane, welding rods, acetylene, oxygen, and etc., had not been trained to recognize and avoid the hazards associated with hazardous chemical products.       29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Recent events (2)
  • · I (O) $1032.75
  • · Z (S) $2065.5

1910.38 F

Other-than-serious 1 instance 30 exposed
Issued
Apr 30, 2012
Abate by
Jun 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.38(f):     Review of emergency action plan. An employer must review the emergency action plan with each employee covered by the plan:    Employee(s) working at the establishment were not provided training covering the emergency action plan that instructs employee(s) of the action necessary when carrying out an immediate evacuation due to fire, toxic chemicals, and tornados.    29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Abc/Fry-Wagner, INC.'s full OSHA safety record →