TONOPAH, NV ·
OSHA Inspection: BUREAU OF LAND MANAGEMENT - TONOPAH FIELD OFFICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUREAU OF LAND MANAGEMENT - TONOPAH FIELD OFFICE in 1553 S. MAIN STREET, TONOPAH, NV 89049 (NAICS 924120). OSHA activity number 332835958.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUREAU OF LAND MANAGEMENT - TONOPAH FIELD OFFICE
- Site address
- 1553 S. MAIN STREET
- City
- TONOPAH
- State
- NV
- ZIP
- 89049
- Mailing
- 1553 S. MAIN STREET, TONOPAH, NV 89049
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 50
- Ownership type
- Federal government (D)
Citations
10 citations on file for this inspection.
1910.22 B01
- Issued
- Jul 2, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(b)(1): The employer did not ensure that aisles and passageways were kept clear and in good repair, with no obstruction across or in aisles that could create a hazard. (a) At the BLM, Tonopah field office, North of ROCO bldg., 1553 S. Main Street, stairway was not properly secured, stair post were not anchored to the ground and the end of the handicap ramp was supported by a stock of wood blocks.
Recent events (1)
- · Z (S) $0
1910.24 F
- Issued
- Jul 2, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.24(f): Rise height and tread width were not uniform throughout any flight of stairs including any foundation structure used as one or more treads of the stairs: (a) At the BLM, Tonopah field office, North of ROCO bldg., 1553 S. Main Street, stairway risers from the ground to the first steps were 14.5 and 12 inches. All other risers were 6 inches.
Recent events (1)
- · Z (S) $0
1910.36 G02
- Issued
- Jul 2, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): The exit access was not at least 28 inches (71.1 cm) wide at all points. Where there is only one exit access leading to an exit or exit discharge, the width of the exit and exit discharge was not at least equal to the width of the exit access. (a) At the hydrologist's cubicle, the exit access was approximately 12 inches wide and obstructed by plastic containers.
Recent events (1)
- · Z (S) $0
1910.37 B05
- Issued
- Jul 2, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet). (a) At the BLM computer room and at the RECO bldg., the door leading to the UPS room and the phone room were not labeled "NOT AN EXIT".
Recent events (1)
- · Z (S) $0
1910.157 C01
- Issued
- Jul 2, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. (b) At the BLM warehouse and covered parking lot storage, a portable fire extinguishers was left standing, unsecured and blocked by metal cabinet and safe.
Recent events (1)
- · Z (S) $0
1910.303 B02
- Issued
- Jul 2, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment were not installed and used in accordance with any instructions included in the listing or labeling. (a) At the BLM RECO Bldg., a relocatable power tap was used to plug-in the air tech electric space heater.
Recent events (1)
- · Z (S) $0
1910.305 A02 X
- Issued
- Jul 2, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points. (a) At the outside yard vehicle parking, a blue flexible extension cord was run along the graveled vehicle parking and exposed to the elements.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV A
- Issued
- Jul 2, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cord was used as a substitute for the fixed wiring of a structure; (a) At the BLM outside yard, a yellow extension cord was used to provide power for the back flow preventer.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV B
- Issued
- Jul 2, 2012
- Abate by
- Jul 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): The employer failed to ensure that flexible cord were not run through holes in walls, ceilings, or floors; (a) At the BLM outside yard, a yellow extension cord was run under the wall of the back flow preventer shed.
Recent events (1)
- · Z (S) $0
1910.159 C10
- Issued
- Jul 2, 2012
- Abate by
- Jul 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The employer did not assure that sprinklers are spaced to provide a maximum protection area per sprinkler, a minimum of interference to the discharge pattern by building or structural members or building contents and suitable sensitivity to possible fire hazards. The minimum vertical clearance between sprinklers and material below was not 18 inches (45.7 cm). (a) At the janitor's closet, cleaning gear and other materials stored in shelves were obstructing the sprinkler head.
Recent events (1)
- · Z (O) $0
More inspections at Bureau of Land Management - Tonopah Field Office
View Bureau of Land Management - Tonopah Field Office's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 332835958.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.