Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ELEMENTIS SPECIALTIES

Unprogrammed Related inspection · Health discipline

On , OSHA opened an unprogrammed Related health inspection of ELEMENTIS SPECIALTIES in 5548 MANCHESTER AVENUE, SAINT LOUIS, MO 63110 (NAICS 325131). OSHA activity number 333296150.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Elementis Specialties — free Get an email when a new federal OSHA severe-injury report for Elementis Specialties is published. One employer, no account, unsubscribe in one click.
Site address
5548 MANCHESTER AVENUE
City
SAINT LOUIS
State
MO
ZIP
63110
Mailing
5548 MANCHESTER AVENUE, SAINT LOUIS, MO 63110
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325131
Employees
65
Ownership type
A

12 citations on file for this inspection.

1910.22 A01

Other-than-serious 1 instance 6 exposed
Issued
Jul 17, 2012
Penalty
Initial $4,250 · Current $3,400 Reduced
29 CFR 1910.22(a)(1):     All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition:    a. In the Betone packing area, combustible dust had accumulated on surfaces, including building structure surfaces, piping, conduit, equipment support; dust levels were measured at depths greater than 1/8 inch; a housekeeping program had not been established to control dust accumulation.  (Note: an example standard for acceptable dust accumulation is NFPA 654.)
Recent events (2)
  • — I (O) $3400
  • — Z (S) $4250

1910.307 C

Other-than-serious 1 instance 6 exposed
Issued
Jul 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c):     Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:    a. In the Betone packing area, combustible dust had accumulated on surfaces, including building structure surfaces, piping, conduit, equipment support, where there were examples of general electrical wiring and equipment; dust levels were measured at depths greater than 1/8 inch; a housekeeping program had not been established to control dust accumulation.  (Note: upon the establishment of a housekeeping program that controls dust, such as explained in NFPA 654, electrical wiring and equipment for a hazardous location is not required.)
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.119 D03 I B

Other-than-serious 1 instance 12 exposed
Issued
Jul 17, 2012
Abate by
Sep 19, 2012
Penalty
Initial $4,250 · Current $3,400 Reduced
29 CFR 1910.119(d)(3)(i)(B):     The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process:    a. Not all equipment was included on P&ID's or was not accurate, such as, but not limited to, valve V0208 (Drawing 143-D102) was not present on the TDI line.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (O) $3400
  • — Z (S) $4250

1910.119 J02

Other-than-serious 2 instances 12 exposed
Issued
Jul 17, 2012
Abate by
Mar 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.119(j)(2):     The employer did not implement written procedures to maintain the on-going integrity of process equipment    a. Equipment was not labeled as required by company procedures with specific identifying numbers (MI001, 3.1, 7.1, 7.2; MI020, 5.1.3), such as, but not limited to, manual valve V0232.  (Note: at the time of the inspection equipment was in the process of being identified and labeled, but much of the equipment was not labeled.)    b. Not all equipment was inspected as required by company procedures to ensure mechanical integrity of equipment, such as pressure relief PSV-309 (set at 325 psi, for system pressure of 300 psi).    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.119 F03

Other-than-serious 1 instance 45 exposed
Issued
Jul 17, 2012
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.119(f)(3):     The employer did not annually certify that operating procedures were current and accurate:    a. Operating procedures had not been certified annually.
Recent events (2)
  • — I (O) $2125
  • — Z (S) $4250

1910.119 E06

Deleted Serious Gravity 5 1 instance 45 exposed
Issued
Jul 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.119(e)(6):     The process hazard analysis was not updated and revalidated every five years:    a. Process hazard analyses were conducted in 2001 and 2009; the five year frequency for updating was not accomplished.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.119 O01

Deleted Serious Gravity 5 1 instance 45 exposed
Issued
Jul 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.119(o)(1):     The employer did not certify that they had evaluated compliance with the provisions of this section (compliance audit) at least every three years:    a. Compliance audits were conducted in 2001 and 2010; the three year frequency for updating was not accomplished.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.119 G01 I

Serious Gravity 5 1 instance 3 exposed
Issued
Jul 17, 2012
Abate by
Sep 19, 2012
Penalty
Initial $4,250 · Current $3,400 Reduced
29 CFR 1910.119(g)(1)(i):     The employer did not train each employee in an overview of the process:    a. Not all employees (including operators and maintenance) were trained on the process safety management overview and hazards associated with the process.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $3400
  • — Z (S) $4250

1910.119 J04 I

Serious Gravity 5 1 instance 12 exposed
Issued
Jul 17, 2012
Abate by
Mar 19, 2013
Penalty
Initial $4,250 · Current $3,400 Reduced
29 CFR 1910.119(j)(4)(i):     The employer did not perform inspection and tests on process equipment:    a. There was no inspection on equipment such as, PSV-309 and internal integrity of reactor vessels.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $3400
  • — Z (S) $4250

1910.119 J04 III

Serious Gravity 5 1 instance 12 exposed
Issued
Jul 17, 2012
Abate by
Mar 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.119(j)(4)(iii):     The frequency of inspections and tests of process equipment were not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience:    a. There was no inspection on equipment such as, the internal reactor vessels, and inspection frequency was deficient in identifying the dismantled actuator valve FV301-4 or proper relief for PSV-309.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.119 J04 IV

Serious 1 instance 12 exposed
Issued
Jul 17, 2012
Abate by
Mar 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.119(j)(4)(iv):     The employer did not document each inspection and test that was performed on process equipment:     a. There was no inspection documentation on all valves, such as, but not limited to, PSV-309 and FV301-4.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.119 J05

Serious 1 instance 12 exposed
Issued
Jul 17, 2012
Abate by
Sep 19, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.119(j)(5):     The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section):    a. During the inspection, there were examples of valves that were not functioning as designed or were not set to provide designed protection, such as FV301-4 and PSV-309.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Elementis Specialties's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 333296150.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.