OSHA Inspection: NOMAC DRILLING COMPANY LLC RIG 11

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NOMAC DRILLING COMPANY LLC RIG 11 in 4 MI E OF ELK CITY ON OLD 66 N HANNAH-ROY TRUST 17-11-20-1H, ELK CITY, OK 73036 (NAICS 213111). OSHA activity number 333884625.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nomac Drilling Company LLC RIG 11 — free Get an email when a new federal OSHA severe-injury report for Nomac Drilling Company LLC RIG 11 is published. One employer, no account, unsubscribe in one click.
Site address
4 MI E OF ELK CITY ON OLD 66 N HANNAH-ROY TRUST 17-11-20-1H
City
ELK CITY
State
OK
ZIP
73036
Mailing
3400 SOUTH RADIO ROAD, EL RENO, OK 73036
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
23
Ownership type
A

3 citations on file for this inspection.

1910.305 B02 I

Other-than-serious 23 exposed
Issued
Apr 24, 2012
Abate by
Apr 25, 2012
Penalty
Initial $5,500 · Current $5,500
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose:    On or about April 13, 2012, the covers for the conductors for the MCC trailer were not installed.  They were located inside the trailer in a table drawer.  This condition exposed worker to 480 VAC main power to the rig and an hazard of electruction.  The opening was on the side of the MCC trailer exposed to the generator house.
Recent events (2)
  • — I (O) $5500
  • — Z (S) $5500

1910.305 G02 I

Other-than-serious 1 instance 23 exposed
Issued
Apr 24, 2012
Abate by
Apr 25, 2012
Penalty
Initial $5,500 · Current $0 Reduced
29 CFR 1910.305(g)(2)(i): A conductor of a flexible cord or cable that is used as a grounded conductor or an equipment grounding conductor shall be distinguishable from other conductors. Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, and STOO flexible cords and Types G, G-GC, PPE, and W flexible cables shall be durably marked on the surface at intervals not exceeding 610 mm (24 in.) with the type designation, size, and number of conductors:    On or about April 13, 2012, a SPT type cord without a grounding conductor was used the energize a refrigator.  Food was being stored in the refrigator, located in the mud house.  This condition exposed workers to the hazard of electrocution.
Recent events (2)
  • — I (O) $0
  • — Z (S) $5500

1910.305 G02 III

Other-than-serious 23 exposed
Issued
Apr 24, 2012
Abate by
Apr 25, 2012
Penalty
Initial $5,500 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    On or about April 13, 2012, the strain relief devices were not effective creating an electrical hazard to workers:         a.  Black cord on the top row of outlets third from the right, located on the rig floor.  110 VAC cord had the outer sheath pulled back to a point the clamp would not seat.         b.  Black cord to well logger's trailer, located on the transformer provided power for the trailers.  110 VAC cord was too small for the strain relief device.         c.  Entrance cable to panel mounted to company man's trailer did not have a strain relief device.    Employees were exposed to hazards from electrical shock.