OSHA Inspection: GENESIS HEALTHCARE LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of GENESIS HEALTHCARE LLC in 590 NORTH POPLAR FORK ROAD, HURRICANE, WV 25526 (NAICS 623110). OSHA activity number 334089653.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Genesis Healthcare LLC — free Get an email when a new federal OSHA severe-injury report for Genesis Healthcare LLC is published. One employer, no account, unsubscribe in one click.
Site address
590 NORTH POPLAR FORK ROAD
City
HURRICANE
State
WV
ZIP
25526
Mailing
590 NORTH POPLAR FORK ROAD, HURRICANE, WV 25526
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
250
Ownership type
A

5 citations on file for this inspection.

1910.303 G01

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 16, 2012
Abate by
Jul 17, 2012
Penalty
Initial $4,000 · Current $3,000 Reduced
29 CFR 1910.303(g)(1):     Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment    (a) Laundry Area: The electrical disconnect for the Wascomate Washing Machine, s/n 10300020, was blocked by various PVC pipe and electrical wiring preventing the employee safe access to the main disconnect, as determined on or about 04/23/2012.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.303 G01 I A

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 16, 2012
Abate by
Jul 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(A):     For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    (a) Laundry Area: An employee conducts maintenance work on the washing machines such as a Wascomat, s/n 10300020, which requires control of hazardous energy. To gain access to the rear of the washing machines to examine, adjust, or service an employee's access is limited to 19 inches horizontally. A minimum working space of 30 inches horizontally was not provided, as determined on or about 04/23/2012.      ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.23 A09

Other-than-serious 1 instance 1 exposed
Issued
Jul 16, 2012
Abate by
Jul 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.23(a)(9):     Floor hole(s) into which persons could not accidentally walk were not protected by securely held covers:    (a) Laundry Area: An employee conducts maintenance work on the washing machines such as a Wascomat, s/n 10300020, which requires access to the rear of the machine. A 6 inch by 6 inch hole was not covered to prevent materials and tools from falling in, as determined on or about 04/23/2012.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.147 C06 I

Other-than-serious 1 instance 1 exposed
Issued
Jul 16, 2012
Abate by
Jul 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i):     The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    (a) Facility Wide: Maintenance employees perform maintenance and service on machinery such as, but not limited to the Wascomat, s/n 10300020, 220 volt three phase washing machine and requires the control of hazardous energy by locking out the equipment.  The employer has not conducted a periodic inspection of the energy control procedures, as determined on or about 04/23/2012.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B02 I

Other-than-serious 1 instance 1 exposed
Issued
Jul 16, 2012
Abate by
Jul 17, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i):     Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    (a) Laundry Area: An employee was using an electrical outlet to power a Lasko brand oscillating fan. The outlet did not have a faceplate to cover the outlet opening exposing the internal wiring to accumulated dust, as observed on or about 04/23/2012.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Genesis Healthcare LLC's full OSHA safety record →