BROWNSVILLE, TX ·
OSHA Inspection: NOBLE DRILLING SERVICES, INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of NOBLE DRILLING SERVICES, INC. in 20000 STATE HIGHWAY 48 EAST VESSEL NOBLE SAM NOBLE, BROWNSVILLE, TX 78523 (NAICS 213111). OSHA activity number 334121621.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NOBLE DRILLING SERVICES, INC.
- Site address
- 20000 STATE HIGHWAY 48 EAST VESSEL NOBLE SAM NOBLE
- City
- BROWNSVILLE
- State
- TX
- ZIP
- 78523
- Mailing
- 13135 SOUTH DAIRY ASHFORD, SUITE 800, SUGAR LAND, TX 77478
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213111
- Employees
- 14
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1915.12 F
- Issued
- Oct 24, 2012
- Abate by
- Nov 15, 2012
- Penalty
- Initial $7,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1915.12(f): Each employer whose employees work in confined and enclosed spaces or other dangerous atmospheres did not ensure all available information on the hazards, safety rules, and emergency procedures concerning those spaces and atmospheres were exchanged with any other employer whose employees may enter the same spaces. In the water maker room on the vessel Noble Sam Noble, located on the floating dry dock of Keppel AmFELS, LLC, contract employees were working on the twenty-six bottle carbon dioxide fire suppression system. The employer failed to notify all employees working in adjacent rooms or areas of potential hazards including but not limited to release of carbon dioxide, oxygen deficient atmosphere and asphyxiation.
Recent events (3)
- · F (O) $1500
- · C (S) $7000
- · Z (S) $7000
1915.89 L02 II
- Issued
- Oct 24, 2012
- Abate by
- Nov 15, 2012
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1915.89(l)(2)(ii): The host employer did not instruct each contract employer to follow its lockout/tags-plus program and procedures: In the water maker room on the vessel Noble Sam Noble, located on the floating dry dock of Keppel AmFELS, LLC, a contract employer assigned to conduct maintenance on the twenty-six bottle Carbon Dioxide fire suppression system was not informed of or instructed to use Noble Drilling Services' lockout/tags plus program and procedures.
Recent events (3)
- · F (O) $0
- · C (S) $7000
- · Z (S) $7000
1915.89 L02 I
- Issued
- Oct 24, 2012
- Abate by
- Nov 15, 2012
- Penalty
- Initial $7,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1915.89(l)(2)(i): In a multi-employer worksite, the host employer did not inform each contract employer about the content of the host employer's lockout/tags-plus program and procedures: In the water maker room on the vessel Noble Sam Noble, located on the floating dry dock of AmFELS, LLC, contract employees, when servicing a twenty-six bottle carbon dioxide fire suppression system, were not informed to lockout, secure and/or isolate the system prior to working on it which exposed employees to an asphyxiation hazard.
Recent events (3)
- · F (O) $1500
- · C (S) $7000
- · Z (S) $7000
1915.506 F
- Issued
- Oct 24, 2012
- Abate by
- Nov 15, 2012
- Penalty
- Initial $7,000 · Current $5,000 Reduced
General-duty citation text
29 CFR 1915.506(f): Before conducting maintenance on a fixed extinguishing system, the employer did not ensure the system was physically isolated: In the water maker room, on the vessel Noble Sam Noble, located on the floating dry dock of Keppel AmFELS, LLC, contract employees were assigned to service and test the twenty-six bottle carbon dioxide fire suppression system. A means to isolate the system from the protected areas during the servicing operation was not provided or used.
Recent events (3)
- · F (S) $5000
- · C (S) $7000
- · Z (S) $7000
More inspections at Noble Drilling Services, INC.
View Noble Drilling Services, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 213111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334121621.