Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SENIOR AEROSPACE CONNECTICUT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SENIOR AEROSPACE CONNECTICUT in 4 PEERLESS WAY, ENFIELD, CT 06082 (NAICS 332710). OSHA activity number 334495561.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Senior Aerospace Connecticut — free Get an email when a new federal OSHA severe-injury report for Senior Aerospace Connecticut is published. One employer, no account, unsubscribe in one click.
Site address
4 PEERLESS WAY
City
ENFIELD
State
CT
ZIP
06082
Mailing
4 PEERLESS WAY, ENFIELD, CT 06082
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
89
Ownership type
A

5 citations on file for this inspection.

1910.157 G02

Serious Gravity 1 45 instances 87 exposed
Issued
Aug 6, 2012
Abate by
Sep 18, 2012
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1910.157(g)(2):  The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter:      The employer had not provided annual fire extinguisher refresher training since September 2010.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2550

1910.242 B

Serious Gravity 1 10 instances 87 exposed
Issued
Aug 6, 2012
Abate by
Sep 18, 2012
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1910.242(b):  Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:          At locations throughout the facility, including at the Sharp #65 milling machine in the Manual Department, compressed air used for cleaning purposed was not reduced to below 30 p.s.i.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2550

1910.305 B01 II

Serious Gravity 5 1 instance 89 exposed
Issued
Aug 6, 2012
Abate by
Sep 18, 2012
Penalty
Initial $3,400 · Current $2,380 Reduced
29 CFR 1910.305(b)(1)(ii):  Unused openings in boxes, cabinets, or fittings were not effectively closed:          At electrical subpanel PP3:  An unused opening was not effectively closed with a breaker or blank, exposing employees to electric shock hazards.
Recent events (2)
  • — I (S) $2380
  • — Z (S) $3400

1910.178 A05

Other-than-serious 1 instance 6 exposed
Issued
Aug 6, 2012
Abate by
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.178(a)(5):  When trucks are equipped with front-end attachments other than factory installed attachments, it was not requested that the truck be marked to identify the attachments and show the approximate weight of the truck and attachment combination at maximum elevation with load laterally centered:        Production Floor:  Caterpillar M40, S/N 23NO2298 powered industrial truck was provided with 60" fork attachments.  The data plate had not been marked to identify the attachments, or show the weight of the truck and attachment combination at a maximum elevation with load laterally centered.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 B02

Other-than-serious 10 instances 87 exposed
Issued
Aug 6, 2012
Abate by
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:        At locations throughout the facility, including the Assembly Area at MSI monitor "Shop 07":  Wall-mount listed electrical outlet boxes with knockouts were used as pendant drops to provide power to equipment.
Recent events (2)