OSHA Inspection: DEPARTMENT OF THE INTERIOR, BUREAU OF RECLAMATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF THE INTERIOR, BUREAU OF RECLAMATION in ADMINISTRATION BLDG. 1200 PARK STREET, BOULDER CITY, NV 89005 (NAICS 921110). OSHA activity number 334826799.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of the Interior, Bureau of Reclamation for free Get an email when a new federal OSHA severe-injury report for Department of the Interior, Bureau of Reclamation is published. One employer, no account, unsubscribe in one click.
Site address
ADMINISTRATION BLDG. 1200 PARK STREET
City
BOULDER CITY
State
NV
ZIP
89005
Mailing
PO BOX 61470, BOULDER CITY, NV 89006
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
921110
Employees
850
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 6 instances 53 exposed
Issued
Oct 2, 2012
Abate by
Oct 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2):  Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.    (a)  Bureau of Reclamation, Administration and Administration Annex Buildings, exit access ranged from 15 to 26 inches for rooms A304, A305, A306, AA127, AA106, and AA107.
Recent events (1)
  • · Z (S) $0

1910.37 B05

Serious Gravity 1 2 instances 95 exposed
Issued
Oct 2, 2012
Abate by
Oct 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5):  Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet).    (a)  Bureau of Reclamation, Administration and Administration Buildings; the door leading to storage from the secretary's office and the door leading to the hallway from the procurement clerk's office could be mistaken for an exit and was not marked "NOT AN EXIT"
Recent events (1)
  • · Z (S) $0

1910.157 C01

Serious Gravity 1 1 instance 45 exposed
Issued
Oct 2, 2012
Abate by
Oct 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):   Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.    (a)  Bureau of Reclamation, Administration Building, portable fire extinguisher in the hallway was blocked by recycling containers.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 1 5 instances 15 exposed
Issued
Oct 2, 2012
Abate by
Oct 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):   Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.    (a)  Bureau of Reclamation, Administration and Administration AnnexBuilding, relocatable power taps were not used in accordance with instructions included in the listing or labeling:           1.  Class placement manager's office, a relocatable power tap was used to plug in a refrigerator and a coffee maker.         2.  Regional Director's Office, relocatable power taps were daisy chained.         3.  Executive Assistant Office, relocatable power taps were daisy chained.         4.  Regional IT security manager's office, relocatable power tap connected to an extension cord.         5.  Security Office, a relocatable power tap was used to plug-in a microwave oven and a refrigerator.
Recent events (1)
  • · Z (S) $0

1910.303 H05 III B

Serious Gravity 5 1 instance 43 exposed
Issued
Oct 2, 2012
Abate by
Oct 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(h)(5)(iii)(B):   Permanent and conspicuous warning signs were not provided, reading substantially as follows: "DANGER -- HIGH VOLTAGE -- KEEP OUT."    (a)  Bureau of Reclamation, Administration Buiilding, main building outdoor distribution switchboard power panel did not have a high voltage warning sign.
Recent events (1)
  • · Z (S) $0

1910.304 B03 I

Serious Gravity 5 2 instances 43 exposed
Issued
Oct 2, 2012
Abate by
Oct 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i):   All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel    (a)  Bureau of Reclamation, Administration Buiilding, main office kitchen sink and bunker room sink, the electrical outlets did not have ground fault circuit interrupter protection.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV B

Serious 1 instance 43 exposed
Issued
Oct 2, 2012
Abate by
Oct 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B):  Flexible cords and cables must not be used where run through holes in walls, ceilings, or floors.    (a)  Bureau of Reclamation, Administration Buiilding, security office, flexible cord was run through the ceiling to extend power to the television.
Recent events (1)
  • · Z (S) $0