OSHA Inspection: ACCURATE ELECTRIC CONSTRUCTION, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ACCURATE ELECTRIC CONSTRUCTION, INC. in 401 N. HIGH ST., COLUMBUS, OH 43215 (NAICS 238210). OSHA activity number 334894193.

Watch Accurate Electric Construction, INC. — free Get an email when a new federal OSHA severe-injury report for Accurate Electric Construction, INC. is published. One employer, no account, unsubscribe in one click.
Site address
401 N. HIGH ST.
City
COLUMBUS
State
OH
ZIP
43215
Mailing
6901 AMERICANA PARKWAY, REYNOLDSBURG, OH 43068
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
197
Ownership type
A

2 citations on file for this inspection.

1926.405 G02 V

Serious Gravity 5 1 instance 50 exposed
Issued
Abate by
Penalty
Initial $3060.00 · Current $1377.00 Reduced
29 CFR 1926.405(g)(2)(v):     Cords passing through holes. Flexible cords and cables shall be protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures.    a. On the 7th floor, there was a power cable for the temporary lighting running through a hole on the front of an electrical cabinet with no bushings or fittings, thereby exposing employees to a contact hazard.
Recent events (2)
  • — I (S) $1377
  • — Z (S) $3060

1926.416 A01

Serious Gravity 5 1 instance 50 exposed
Issued
Abate by
Penalty
Initial $4590.00 · Current $2066.00 Reduced
29 CFR 1926.416(a)(1):     No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.    a. On the south side of the 11th floor corridor, there was an exposed energized wire in the temporary lighting system 5 foot 3 inches from the ground, thereby exposing employees to a contact hazard.