OMAHA, NE ·
OSHA Inspection: OMAHA FIXTURE MANUFACTURING, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of OMAHA FIXTURE MANUFACTURING, INC. in 10320 J ST., OMAHA, NE 68127 (NAICS 337215). OSHA activity number 335060380.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OMAHA FIXTURE MANUFACTURING, INC.
- Site address
- 10320 J ST.
- City
- OMAHA
- State
- NE
- ZIP
- 68127
- Mailing
- 10320 J ST., OMAHA, NE 68127
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337215
- Employees
- 37
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
1910.151 C
- Issued
- Oct 19, 2012
- Abate by
- Dec 4, 2012
- Penalty
- Initial $2,800 · Current $1,540 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use. An appropriate eyewash station was not available in work area near the east wall battery charging station of Plant #2. Employees are exposed to corrrosive battery acid.
Recent events (2)
- · I (S) $1540
- · Z (S) $2800
1910.178 L01 I
- Issued
- Oct 19, 2012
- Abate by
- Dec 4, 2012
- Penalty
- Initial $3,500 · Current $1,925 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l). Employee(s) operating stand-up forklifts, had not received the training and evaluation required by the standard.
Recent events (2)
- · I (S) $1925
- · Z (S) $3500
1910.303 B02
- Issued
- Oct 19, 2012
- Abate by
- Jan 18, 2013
- Penalty
- Initial $2,800 · Current $1,540 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. The listed items had the following deficiencies: A) Mounting type outlet boxes were used as hanging "pendant" boxes throughout Plants #1 and #2 in areas including, but not limited to the shipping station and the receiving cube. B) Relocatable power taps (power strips) were used to power a variety of equipment throughout Plants #1 and#2 including, not limited to chargers and phone back-up system. Some of the power strips were mounted to building surfaces.
Recent events (2)
- · I (S) $1540
- · Z (S) $2800
1910.305 B01 II
- Issued
- Oct 19, 2012
- Abate by
- Jan 18, 2013
- Penalty
- Initial $3,500 · Current $1,925 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. An unused opening in an electrical panel box near a battery charging station in Plant #2, was not covered exposing live wiring.
Recent events (2)
- · I (S) $1925
- · Z (S) $3500
1910.305 G01 IV
- Issued
- Oct 19, 2012
- Abate by
- Jan 18, 2013
- Penalty
- Initial $2,800 · Current $1,540 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv) in the following instances: A) Flexible cords for multiple outlet boxes were used as a substitute for fixed wiring throughout Plants #1 and #2. B) Flexible cord for the shrink wrap unit in Plant #2 was attached in multiple locations to adjacent racking.
Recent events (2)
- · I (S) $1540
- · Z (S) $2800
1910.1200 E01
- Issued
- Oct 19, 2012
- Abate by
- Jan 18, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met A written chemical hazard communication program was not available upon agency request. Employee(s) are exposed to chemicals including, but not limited to isopropryl alcohol and NPE Cleaning Fluid.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at Omaha Fixture Manufacturing, INC.
View Omaha Fixture Manufacturing, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 337215)
More inspections in NE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 335060380.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.