BROOKLYN, NY ·
OSHA Inspection: CONSOLIDATED EDISON COMPANY OF NEW YORK, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. in 1274 MCDONALD AVENUE, BROOKLYN, NY 11230 (NAICS 221122). OSHA activity number 335098786.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONSOLIDATED EDISON COMPANY OF NEW YORK, INC.
- Site address
- 1274 MCDONALD AVENUE
- City
- BROOKLYN
- State
- NY
- ZIP
- 11230
- Mailing
- 4 IRVING PLACE, 15 FLOOR NE, NEW YORK, NY 10003
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 10
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1910.132 D01 I
- Issued
- Dec 31, 2012
- Abate by
- Jan 18, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.132(d)(1)(i): Select, and have each affected employee use, the types of PPE that will protect the affected employee from the hazards identified in the hazard assessment; Location: 4 East section of the substation; On or about 07/02/12; a) Employees did not use personal protective equipment for potential arc flash when racking a 27KV circuit breaker.
Recent events (3)
- · F (S) $0
- · C (S) $7000
- · Z (S) $7000
1910.269 A02 II D
- Issued
- Dec 31, 2012
- Abate by
- Jan 18, 2013
- Penalty
- Initial $5,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(a)(2)(ii)(D): The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment. Note: For the purposes of this section, a person must have this training in order to be considered a qualified person. Location: 4 East section of substation; On or about 07/02/12; a) Employees were not familiar and did not use appropriate personal protective equipment when performing a racking operation on a circuit breaker in a live electrical panel.
Recent events (3)
- · F (S) $0
- · C (S) $5500
- · Z (S) $5500
1910.269 C01
- Issued
- Dec 31, 2012
- Abate by
- Jan 18, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(c)(1): If the work or operations to be performed during the work day or shift are repetitive and similar, at least one job briefing shall be conducted before the start of the first job of each day or shift. Additional job briefings shall be held if significant changes, which might affect the safety of the employees, occur during the course of the work. Location: 4 East section of substation; On or about 07/02/12; a) A job briefing for the assistant was not conducted by the Supervisor prior to the racking of the circuit breaker in the live electrical panel.
Recent events (3)
- · F (S) $0
- · C (S) $0
- · Z (S) $0
More inspections at Consolidated Edison Company of NEW York, INC.
View Consolidated Edison Company of NEW York, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 335098786.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.