Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: CONSOLIDATED EDISON COMPANY OF NEW YORK, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. in 1274 MCDONALD AVENUE, BROOKLYN, NY 11230 (NAICS 221122). OSHA activity number 335098786.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Consolidated Edison Company of NEW York, INC. for free Get an email when a new federal OSHA severe-injury report for Consolidated Edison Company of NEW York, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1274 MCDONALD AVENUE
City
BROOKLYN
State
NY
ZIP
11230
Mailing
4 IRVING PLACE, 15 FLOOR NE, NEW YORK, NY 10003
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
10
Ownership type
Private (A)

3 citations on file for this inspection.

1910.132 D01 I

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Dec 31, 2012
Abate by
Jan 18, 2013
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.132(d)(1)(i): Select, and have each affected employee use, the types of PPE that will protect the affected employee from the hazards identified in the hazard assessment;    Location: 4 East section of the substation;    On or about 07/02/12;    a) Employees did not use personal protective equipment for potential arc flash when racking a 27KV circuit breaker.
Recent events (3)
  • · F (S) $0
  • · C (S) $7000
  • · Z (S) $7000

1910.269 A02 II D

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Dec 31, 2012
Abate by
Jan 18, 2013
Penalty
Initial $5,500 · Current $0 Reduced
29 CFR 1910.269(a)(2)(ii)(D): The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment.   Note: For the purposes of this section, a person must have this training in order to be considered a qualified person.    Location: 4 East section of substation;    On or about 07/02/12;    a) Employees were not familiar and did not use appropriate personal protective equipment when performing a racking operation on a circuit breaker in a live electrical panel.
Recent events (3)
  • · F (S) $0
  • · C (S) $5500
  • · Z (S) $5500

1910.269 C01

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Dec 31, 2012
Abate by
Jan 18, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.269(c)(1): If the work or operations to be performed during the work day or shift are repetitive and similar, at least one job briefing shall be conducted before the start of the first job of each day or shift. Additional job briefings shall be held if significant changes, which might affect the safety of the employees, occur during the course of the work.    Location: 4 East section of substation;    On or about 07/02/12;    a) A job briefing for the assistant was not conducted by the Supervisor prior to the racking of the circuit breaker in the live electrical panel.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

View Consolidated Edison Company of NEW York, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 335098786.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.