SCHENECTADY, NY —
OSHA Inspection: THE GOLUB CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of THE GOLUB CORPORATION in 501 DUANESBURG RD., SCHENECTADY, NY 12306 (NAICS 493110). OSHA activity number 335294781.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE GOLUB CORPORATION
- Site address
- 501 DUANESBURG RD.
- City
- SCHENECTADY
- State
- NY
- ZIP
- 12306
- Mailing
- 501 DUANESBURG RD., SCHENECTADY, NY 12306
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 1200
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.134 H03 I B
- Issued
- Dec 4, 2012
- Penalty
- Initial $3,400 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.134(h)(3)(i)(B): Respirators maintained for use in emergency situations were not inspected at least monthly and in accordance with manufacturer recommendations: (a) Response trailer - on or about July 19, 2012, monthly inspection procedure for eight (8) Scott Air Paks 4.5 did not follow the manufacturer's recommendations.
Recent events (2)
- — I (S) $2500
- — Z (S) $3400
1910.119 D03 II
- Issued
- Dec 4, 2012
- Abate by
- Jan 8, 2013
- Penalty
- Initial $4,250 · Current $4,250
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. a) Roof of main building- On or about July 18, 2012, the pressure relief valves for the Low Temp Suction AU#1-#13& 39 were installed to discharge approximately 57 inches above the roof line of the building.
Recent events (2)
- — I (S) $4250
- — Z (S) $4250
1910.119 E03 V
- Issued
- Dec 4, 2012
- Abate by
- Jan 8, 2013
- Penalty
- Initial $4,250 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address facility siting. A) Roof of main building- On July 18, 2012, and at times prior thereto, the process hazard analysis did not address facility siting hazards associate with location of pressure relief valve(s) for air handling units on the roof and proximity to employee work location(s).
Recent events (2)
- — I (S) $0
- — Z (S) $4250
1910.305 G01 IV A
- Issued
- Dec 4, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure. (a) Mechanical Room - On or about July 18, 2012, a flexible 120 V cord was used to power to a solenoid on the air compressor for the pneumatic valves.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at The Golub Corporation
View The Golub Corporation's full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335294781.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.