BOSTON, MA ·
OSHA Inspection: RP/HH PARK PLAZA LIMITED PARTNERSHIP
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of RP/HH PARK PLAZA LIMITED PARTNERSHIP in 50 PARK PLAZA, BOSTON, MA 02116 (NAICS 721110). OSHA activity number 335406997.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RP/HH PARK PLAZA LIMITED PARTNERSHIP
- Site address
- 50 PARK PLAZA
- City
- BOSTON
- State
- MA
- ZIP
- 02116
- Mailing
- 50 PARK PLAZA, BOSTON, MA 02116
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 25
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 B01
- Issued
- Nov 6, 2012
- Abate by
- Feb 7, 2013
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1): Location: Sitewide. Employees were exposed to electrical hazards where a competent person had not taken appropriate steps to abate several unsafe conditions pertaining to electrical equipment throughout the building.
Recent events (2)
- · I (S) $7000
- · Z (S) $7000
1910.303 G02 I
- Issued
- Nov 6, 2012
- Abate by
- Dec 28, 2012
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Jobsite: Several locations throughout building. Employees were exposed to electric shock, arc flash/blast, and other electrical hazards while working on or in close proximity to electrical panels that were missing covers and inner bezels, exposing the live busbars and other live parts within.
Recent events (2)
- · I (S) $0
- · Z (S) $7000
1910.303 B07
- Issued
- Nov 6, 2012
- Abate by
- Nov 29, 2012
- Penalty
- Initial $4,000 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner: Jobsite: Boiler room. Employees were exposed to electrical and fire hazards where: a) Two instances of temporary wiring that had been left in place of a permanent installation where several feet of individual conductors were strung without being housed in a raceway. b) conductor splices had not been placed in a junction box.
Recent events (2)
- · I (S) $2000
- · Z (S) $4000
1910.303 F02
- Issued
- Nov 6, 2012
- Abate by
- Dec 28, 2012
- Penalty
- Initial $5,000 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Jobsite: Kitchen, main mechanical room. Employees were exposed to electrical shock and other hazards while working in and around electrical equipment where the branch circuit breakers in 208 volt, 3-phase panels had not been marked to indicate their purpose.
Recent events (2)
- · I (S) $2500
- · Z (S) $5000
1910.303 G01
- Issued
- Nov 6, 2012
- Abate by
- Nov 13, 2012
- Penalty
- Initial $3,000 · Current $3,000
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment: Jobsite: Kitchen. A three-phase 150 ampere electrical panel was not readily accessible with mops and brooms and a steel storage rack being stored in front of it.
Recent events (2)
- · I (S) $3000
- · Z (S) $3000
1910.304 G05
- Issued
- Nov 6, 2012
- Abate by
- Nov 15, 2012
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. Jobsite: Site. a) The plug on a fan attached to the wall in the kitchen was missing the safety grounding pin. b) The plug on a pedestal fan in the main equipment room was missing the saftey grounding pin.
Recent events (2)
- · I (S) $0
- · Z (S) $3000
More inspections at Rp/Hh Park Plaza Limited Partnership
View Rp/Hh Park Plaza Limited Partnership's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335406997.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.