WILLIAMSVILLE, NY —
OSHA Inspection: HILDRETH ELECTRIC, INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of HILDRETH ELECTRIC, INC in 295 ESSJAY DRIVE, WILLIAMSVILLE, NY 14221 (NAICS 238210). OSHA activity number 335614988.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HILDRETH ELECTRIC, INC
- Site address
- 295 ESSJAY DRIVE
- City
- WILLIAMSVILLE
- State
- NY
- ZIP
- 14221
- Mailing
- PO BOX 555, 5427 CROWN DRIVE, LOCKPORT, NY 14094
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 3
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.403 I02 I
- Issued
- Sep 5, 2012
- Penalty
- Initial $4,200 · Current $2,000 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. a) On or about 8/8/12, at the site of Williamsville, NY. Panel LP-3 (120/208 Volts, 200 Amps) lacked the dead front and panel cover, while there was one employee working in close proximity. No Abatement Certification Required
Recent events (2)
- — I (S) $2000
- — Z (S) $4200
1926.403 I02 III
- Issued
- Sep 5, 2012
- Penalty
- Initial $2,100 · Current $0 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(iii): Entrances to rooms and other guarded locations containing exposed live parts operating at 600 volts, nominal, or less were not marked with conspicuous warning signs forbidding unqualified persons to enter: a) On or about 8/8/12, at the site of Williamsville, NY. Conspicuous warning signs were not provided for Panel LP-1 with exposed, energized live parts. No Abatement Certification Required
Recent events (2)
- — I (O) $0
- — Z (S) $2100
More inspections at Hildreth Electric, INC
View Hildreth Electric, INC's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335614988.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.