ST THOMAS, VI —
OSHA Inspection: SUGAR BAY RESORT & SPA
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SUGAR BAY RESORT & SPA in 6500 ESTATE SMITH BAY, ST THOMAS, VI 00802 (NAICS 721110). OSHA activity number 335667382.
Where did this inspection happen?
- Establishment
- SUGAR BAY RESORT & SPA
- Site address
- 6500 ESTATE SMITH BAY
- City
- ST THOMAS
- State
- VI
- ZIP
- 00802
- Mailing
- 6500 ESTATE SMITH BAY, ST THOMAS, VI 00802
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 340
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.23 A08 I
- Issued
- Abate by
- Penalty
- Initial $3600.00 · Current $3600.00
General-duty citation text
29 CFR 1910.23(a)(8)(i): Every floor hole into which persons could accidentally walk were not guarded by a standard railing with standard toeboard on all exposed sides: a. On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Pool pump room area: Employees were working nearby floor holes in which could accidentally walk and were not guarded by a standard railing with standard toeboard on all exposed sides. Note: Documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(d).
Recent events (4)
- — I $3200
- — I $3200
- — Z $4000
1910.157 C01
- Issued
- Penalty
- Initial $2700.00 · Current $2700.00
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a. On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Mangrove Restaurant area: Employees were working with a portable fire extinguisher that was not wall mounted. Note: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer during the inspection.
Recent events (1)
- — Z (S) $2700
1910.303 G01 I
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: a. On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Mangrove Restaurant electrical panel area: Access to an electrical panel was blocked with metal rack & card board boxes . Note: Certification of abatement must submitted for these citation items as required by 29 CFR 1903.19(c).
Recent events (1)
- — Z (S) $4500
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.303(g)(2)(i):Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: Instance #1 On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Mangrove Restaurant /Food Catering electrical outlet area: Employees were using an electrical outlet without faceplate cover, therefore, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact. Instance #2 On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas Main Kitchen / hallway refrigerator area: Employees were using an electrical refrigerator where its compressor lid cover was missing, therefore, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29. CFR 1903.19(c) and (d), respectively.
Recent events (4)
- — I $4000
- — I $4000
- — Z $5000
1910.304 B03 II A
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that were not part of the permanent wiring of the building or structure and that were in use by personnel did not have ground-fault circuit-interrupter protection for personnel. a. On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Work Shop at Reverse Osmosis plant area: Employees were using electrical power tools connected to an electrical receptacle lacking a ground fault circuit interrupter (GFCI). Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (1)
- — Z (S) $4500
1910.304 G05
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Work Shop at Reverse Osmosis plant area: Employees were using power power tools connected to an electrical outlet box receptacle with no ground. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $4500.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: Instance #1 On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Work Shop at Reverse Osmosis plant area: Employees have been using electrical power tools connected to a metal outlet box. The MT outlet box lacked a face plate cover. Instance #2 On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Mangrove Restaurant /Food Catering electrical outlet area: Employees have been using electrical tools connected to a metal outlet box. The MT outlet box lacked a face plate cover. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively
Recent events (1)
- — Z (S) $4500
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure a. On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Work Shop at Reverse Osmosis plant area: Employees were using an a flexible cord (extention cord) attached to an outlet box used to power tools. NOTE: Documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(d).
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a. On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Work Shop at Reverse Osmosis plant area: Employees were using an electrical welding generator connected to an electrical outlet box receptacle via its equipment electrical cord. The electrical cord was not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. On or about 8/1/2012, Sugar Bay Resort & Spa, 6500 Estate Smith Bay, St Thomas - Mangrove Restaurant area: Employees were using an electrical panel with missing labels. NOTE: Documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(d).
Recent events (1)
- — Z (O) $0
More inspections at SUGAR BAY RESORT & SPA
ST THOMAS, VI—2013-07-31 00:00:00
SUGAR BAY RESORT & SPA
ST THOMAS, VI—2013-07-31 00:00:00
SUGAR BAY RESORT & SPA
ST THOMAS, VI—2012-08-01 00:00:00
SUGAR BAY RESORT & SPA
View SUGAR BAY RESORT & SPA's full OSHA safety record →
More inspections in this industry (NAICS 721110)
LAS VEGAS, NV—2026-07-13
THE BERKLEY LAS VEGAS
LYNCHBURG, VA—2026-07-10
RIVERFRONT HOSPITALITY LLC
INCLINE VILLAGE, NV—2026-07-09
SHANTI RAHM LLC.
INCLINE VILLAGE, NV—2026-07-09
SHANTI RAHM LLC.
ISELIN, NJ—2026-07-09
DELTA HOTELS WOODBRIDGE
More inspections in VI
CHARLOTTE AMALIE, VI—2026-05-26
VIRGIN ISLANDS EMERGENCY MANAGEMENT AGENCY
ST CROIX, VI—2026-05-06
VI DEPARTMENT OF HEALTH
ST CROIX, VI—2026-04-28
GOV. JUAN F. LUIS HOSPITAL
ST CROIX, VI—2026-04-24
GOV. JUAN F. LUIS HOSPITAL
CHRISTIANSTED, VI—2026-04-24
OFFICE OF DISASTER RECOVERY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335667382.