Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DANNEMORA FORD, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DANNEMORA FORD, INC. in 1071 RT 374, DANNEMORA, NY 12929 (NAICS 441110). OSHA activity number 336431390.

Watch Dannemora Ford, INC. — free Get an email when a new federal OSHA severe-injury report for Dannemora Ford, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1071 RT 374
City
DANNEMORA
State
NY
ZIP
12929
Mailing
PO BOX 767, DANNEMORA, NY 12929
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441110
Employees
8
Ownership type
A

7 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $0.00 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees:      a)  Service Area - On or about September 19, 2012, auto repair technicians were exposed to struck-by and caught between hazards while working around and under the Weaver hydraulic auto lift (ModelAFH-90AOH, Serial # 5CP-009).  Hoses were damaged allowing for hydraulic oil leaks.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1910.253 B02 I

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $0.00 Reduced
29 CFR 1910.253(b)(2)(i): Compressed gas cylinders were not kept away from radiators and other sources of heat:    a)  Service Area - On or about September 19, 2012, Oxygen and Acetylene cylinders used for cutting were stored near a pedestal grinder used to grind brake calipers which creates sparks.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1910.253 B04 III

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least:    a)  Service Area - On or about September 19, 2012, an Oxygen cylinder used for cutting was stored next to incompatible materials including an Acetylene cylinder (flammable gas) and SAE 5W20 Motor Oil (combustible liquid) and SAE 5W30 Motor Oil (combustible liquid).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 F02

Serious Gravity 5 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $0.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:      a)  Break room - On or about September 19, 2012, breakers in a panel box were not labeled adequately.     b)  Service Area - On or about September 19, 2012, breakers in a panel box were not labeled adequately.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1910.303 G02 I

Serious Gravity 5 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):      a)  Break Room - On or about September 19, 2012 a breaker panel box did not have a panel door, exposing live electrical components.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    a)  Service Area - On or about September 19, 2012 employees are exposed to burn hazards while working near the electrical panel box (controlling hydraulic lifts) that had a missing knockout.    b)  Used Oil Bay - On or about September 19, 2012 employees are exposed to burn hazards while accessing the electrical panel box (controlling lights) that had two missing knockouts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    a)  Break Room - On or about September 19, 2012, a metal junction box was missing a cover exposing electrical components.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View DANNEMORA FORD, INC.'s full OSHA safety record →