Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HARTMAN ENTERPRISES INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HARTMAN ENTERPRISES INC. in 455 ELIZABETH ST., ONEIDA, NY 13421 (NAICS 332710). OSHA activity number 336447990.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hartman Enterprises INC. — free Get an email when a new federal OSHA severe-injury report for Hartman Enterprises INC. is published. One employer, no account, unsubscribe in one click.
Site address
455 ELIZABETH ST.
City
ONEIDA
State
NY
ZIP
13421
Mailing
PO BOX 360, ONEIDA, NY 13421
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
55
Ownership type
A

9 citations on file for this inspection.

5(a)(1)

Serious Gravity 1 2 instances 2 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $2,100 · Current $1,260 Reduced
Section (5)(a)(1):     The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of being struck by the load should the below-the-hook lifting devices fail:    a)  Saw Area, on or about 9/20/12:  A spreader beam below-the-hook lifting device being used on a Cleveland two ton overhead crane to lift bar stock had no rated load capacity markings and had not been inspected.    b)  Mill Area, on or about 9/20/12:  A below-the-hook lifting device being used on a Cleveland two ton overhead crane for lifting parts into and out of the Mori Seiki CNC mill had no rated load capacity markings and had not been inspected.    Abatement certification must be submitted for these items.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.147 C06 I

Serious Gravity 5 1 instance 20 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $3,500 · Current $2,100 Reduced
29 CFR 1910.147(c)(6)(i):     The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    a)  At the establishment, on or about 9/20/12:  Periodic inspections were not conducted on the energy control procedures to ensure that the lockout/tagout procedures and requirements of the standard were being followed.  Employees perform servicing and/or maintenance on various equipment, including, but not limited to CNC mills, CNC lathes, chip wringer, punch press, saws, etc.    Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3500

1910.147 C07 I

Serious Gravity 5 8 instances 8 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i):     The employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices and to ensure that the purpose and function of the energy control program was understood by employees:    a)  At the establishment, on or about 9/20/12:  Training had not been provided to approximately 8 employees on the lockout/tagout program and procedures to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices and to ensure that the purpose and function of the energy control procedure was understood.    Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 F02

Serious Gravity 1 3 instances 2 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.303(f)(2):     Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    a)  Main Electrical Service across from Tool Crib, on or about 9/20/12:  A circuit breaker panel marked 400 AMP main lug did not have all the breakers labeled as to what they controlled.    b)  Main Shop, behind Mazak Hyper 1, on or about 9/20/12:  Two circuit breaker panels, both marked Building 2, did not have all of the breakers labeled as to what they controlled.    Abatement certification must be submitted for these items.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.304 G05

Serious Gravity 1 3 instances 3 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.304(g)(5):     The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    a)  Deburr Room, on or about 9/20/12:  A portable fan was not grounded in that the ground pin was missing from the plug end.    b)  Back Room, on or about 9/20/12:  A portable fan was not grounded in that the ground pin was missing from the plug end.    c)  Mill Area, on or about 9/20/12:  A portable fan was not grounded at the Akari CNC 6APC mill in that the ground pin was missing from the plug end.    Abatement certification must be submitted for these items.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.304 G06 VI

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(6)(vi):     Exposed noncurrent-carrying metal parts of cord- and plug-connected equipment that could have become energized were not grounded:    a)  Quality Lab, on or about 9/20/12:  A Toastmaster box fan was not grounded in that it had only a two wire cord.    Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.212 A01

Repeat Gravity 5 14 instances 6 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $5,600 · Current $3,360 Reduced
29 CFR 1910.212(a)(1):     Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by rotating parts and ingoing nip points:    a)  Deburr Room,  Deburring Station, on or about 9/20/12:  Rotating chucks on 5 deburring stations and a Rockwell drill press were not guarded.    b)  Main Shop, on or about 9/20/12:  Rotating chucks on a Ridgid drill press #DP15501 next to Mazak Multiplex 2, a Craftsman drill press next to Mazak Multiplex 1 and a Craftsman drill press next to the TW20Y lathe were not guarded.    c)  Back Room, on or about 9/20/12:  Rotating chuck on a Craftsman drill press at the Okuma 400 was not guarded.    d)  Saw Area, on or about 9/20/12:  Ingoing nip points on a chip conveyor for the Kasto vertical bandsaw were not guarded at the discharge end.    e)  Milll Area, on or about 9/20/12:  Unused portion of sanding belt and the spindle end and nut projection on a Baldor belt sander next to Robodrill T14A were not guarded.    f)  Mill Area, on or about 9/20/12:  Rotating chucks and spindles on an Edlund two spindle drill press were not guarded.    Abatement documentation must be submitted for these items.    Hartman Enterprises, Inc. was previously cited for a violation of this Occupational Safety and Health standard which was contained in OSHA Inspection number 310751953, Citation 1, Item 1 and was affirmed as a final order on 12/14/07, with respect to a workplace located at 455 Elizabeth Street, Oneida, New York.
Recent events (2)
  • — I (R) $3360
  • — Z (R) $5600

1910.242 B

Repeat Gravity 1 6 instances 5 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $4,200 · Current $2,520 Reduced
29 CFR 1910.242(b):     Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:    a)  Main Shop, on or about 9/20/12:  Compressed air guns measured >80 psi at, including but not limited to:  Mazak Hyper 1, Mazak Hyper 2, Robodrill T10C, Mazak Dual Turn 20, Mazak Multiplex, TW20Y lathe.    Abatement documentation must be submitted for this item.    Hartman Enterprises, Inc. was previously cited for a violation of this Occupational Safety and Health standard which was contained in OSHA Inspection number 310751953, Citation number 1, item number 2 and was affirmed as a final order on 12/14/07, with respect to a workplace located at 455 Elizabeth Street, Oneida, NY 13421.
Recent events (2)
  • — I (R) $2520
  • — Z (R) $4200

1910.22 A02

Other-than-serious 1 instance 1 exposed
Issued
Oct 9, 2012
Abate by
Oct 16, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(2):     Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition:    a)  Main Shop, on or about 9/20/12:  Coolant was puddled on the floor next to the TW20Y CNC lathe.    Abatement certification must be submitted for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Hartman Enterprises INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336447990.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.