Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SQUARE ONE ARMORING SERVICES CO.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SQUARE ONE ARMORING SERVICES CO. in 12370 SW 130TH STREET, MIAMI, FL 33186 (NAICS 336111). OSHA activity number 336808217.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Square ONE Armoring Services CO. — free Get an email when a new federal OSHA severe-injury report for Square ONE Armoring Services CO. is published. One employer, no account, unsubscribe in one click.
Site address
12370 SW 130TH STREET
City
MIAMI
State
FL
ZIP
33186
Mailing
12370 SW 130TH STREET, MIAMI, FL 33186
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336111
Employees
163
Ownership type
A

6 citations on file for this inspection.

1910.212 A01

Serious Gravity 10 5 instances 5 exposed
Issued
Feb 22, 2013
Abate by
Mar 6, 2013
Penalty
Initial $6,300 · Current $6,300
29 CFR 1910.212(a)(1):  One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    On or about 10/09/2012, employees were exposed to amputation hazards from ingoing nip points while operating belt grinders and a press brake that were lacking point of operation guards to finish metal components at a fabrication facility located at 12370 SW 130 Street, Miami, FL 33186.    5 instances:   Instance A:  # 1 Burr King Belt grinder located in Landcruiser area.  Instance B:  # 2 Burr King Belt grinder located in Landcruiser area.  Instance C:  # 3 Burr King Belt grinder located in Toyota Wagon area.  Instance D:  # 4 Burr King Belt grinder located in Toyota Wagon area.  Instance E:  AccurPress brake lacked point of operation guarding while bending metal components.    NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $6300

1910.303 B01

Serious Gravity 10 4 instances 4 exposed
Issued
Feb 22, 2013
Abate by
Mar 6, 2013
Penalty
Initial $6,300 · Current $6,300
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):    On or about 10/09/2012, employees were exposed to shock and electrocution from using damaged 110 and 220 VAC extension cords and a power strip at a fabrication facility located at 12370 SW 130 Street, Miami, FL 33186.     4 instances:   A. 220 VAC shop built extension cord that was not approved for use powered a Millermatic 252 wire welder. Landcruiser area.    B. Newpoint Model AV 500 power strip with missing ground pin connected to yellow extension cord. Landcruiser area.    C. 110 VAC extension cord with damaged insulation jacket that supplied power to Newpoint Model AV 500 power strip.  Landcruiser area.    D. 220 VAC power cord with damaged insulation jacket at the plug that did not have strain relief that supplied power to Burr King Belt Grinder 3-308 (#1).  Landcruiser area.
Recent events (1)
  • — Z (S) $6300

1910.303 B02

Serious Gravity 10 1 instance 4 exposed
Issued
Feb 22, 2013
Abate by
Mar 6, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    On or about 10/09/2012, employees were exposed to shock and electrocution while using a 220 VAC shop built extension cord that were not approved for use to power a Miller Welding machines at a fabrication facility located at 12370 SW 130 Street, Miami, FL 33186.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 22, 2013
Abate by
Mar 6, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws    On or about 10/09/2012, employees were exposed to shock and electrocution while using a Burr King Belt Grinder, Model 979 that was powered by a 220 VAC cord that had a plug that had damaged outer jacket insulation and lacked strain relief at facility located at 12370 SW 130 Street, Miami, FL 33186.
Recent events (1)
  • — Z (S) $0

1910.334 A02 II

Serious Gravity 10 4 instances 4 exposed
Issued
Feb 22, 2013
Abate by
Mar 6, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service and an employee was using it before repairs and tests necessary to render the equipment safe were made:    On or about 10/09/2012, employees were exposed to shock and electrocution while using damaged and unapproved electrical 110 and 220 VAC electrical cords to power welding machines and task lighting that had not been visually inspected before use at a  facility located at 12370 SW 130 Street, Miami, FL 33186.    4 Instances:     A. 220 VAC shop built extension cord that was not approved for use powered a Millermatic 252 wire welder. Landcruiser area.     B. Newpoint Model AV 500 power strip with missing ground pin connected to yellow extension cord.  Landcruiser area.    C. 110 VAC extension cord with damaged insulation jacket that supplied power to Newpoint Model AV 500 power strip.  Landcruiser area.    D. 220 VAC power cord with damaged insulation jacket at the plug that did not have strain relief that supplied power to Burr King Belt Grinder 3-308. Landcruiser area.
Recent events (1)
  • — Z (S) $0

1910.334 A03 I

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 22, 2013
Abate by
Mar 6, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(3)(i): A flexible cord used with grounding type equipment did not contain an equipment grounding conductor:    On or about 10/09/2012, employees were exposed to shock and electrocution while using a 110 VAC power strip that was lacking a ground pin conductor at a fabrication facility located at 12370 SW 130 Street, Miami, FL 33186.
Recent events (1)
  • — Z (S) $0

View Square ONE Armoring Services CO.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336808217.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.