OSHA Inspection: THE FRESH FISH CO./PROOF NITECLUB

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of THE FRESH FISH CO./PROOF NITECLUB in 7800 E HAMPDEN AVE, DENVER, CO 80231 (NAICS 722210). OSHA activity number 336820584.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Fresh Fish Co./Proof Niteclub — free Get an email when a new federal OSHA severe-injury report for The Fresh Fish Co./Proof Niteclub is published. One employer, no account, unsubscribe in one click.
Site address
7800 E HAMPDEN AVE
City
DENVER
State
CO
ZIP
80231
Mailing
7800 E HAMPDEN AVE, DENVER, CO 80231
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
722210
Employees
95
Ownership type
A

4 citations on file for this inspection.

1910.303 F02

Serious Gravity 1 2 instances 12 exposed
Issued
Feb 14, 2013
Abate by
Mar 12, 2013
Penalty
Initial $1,785 · Current $1,071 Reduced
29 CFR 1910.303(f)(2): Each service, feeder and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    (a)	Fresh Fish Co./Proof Niteclub at 7800 E. Hampden Ave, Denver, CO 80231:  On and before October 11, 2012, the employer did not ensure each circuit breaker was identified in the panel boxes noted as "LA" and an unidentified, smaller breaker panel with six breakers, both in the main electrical room, in that there were missing labels or markings.  This condition exposed the employees to electrical hazards.
Recent events (2)
  • — I (S) $1071
  • — Z (S) $1785

1910.303 G01 I

Serious Gravity 1 2 instances 12 exposed
Issued
Feb 14, 2013
Abate by
Mar 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i):  Workspace was less than 3 feet in front of electric equipment operating at 600 volts nominal, or less:    (a)	Fresh Fish Co./Proof Niteclub at 7800 E. Hampden Ave, Denver, CO 80231:  On and before October 11, 2012, the employer did not maintain workspace of at least 3 feet in front of electrical disconnect switches and circuit breaker panels in the main electrical room in that they were partially obstructed by restaurant equipment and supplies being stored there.  This condition exposed the employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 12 exposed
Issued
Feb 14, 2013
Abate by
Mar 12, 2013
Penalty
Initial $1,785 · Current $1,071 Reduced
29 CFR 1910.305(b)(2)(i):  Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    (a)	Fresh Fish Co./Proof Niteclub at 7800 E. Hampden Ave, Denver, CO 80231:  On and before October 11, 2012, the electrical junction box located above the circuit breaker panels in the main electrical room was uncovered, thus potentially exposing employees to energized parts. This condition exposed the employees to electrical hazards.
Recent events (2)
  • — I (S) $1071
  • — Z (S) $1785

1910.305 G01 IV A

Serious Gravity 1 1 instance 12 exposed
Issued
Feb 14, 2013
Abate by
Mar 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure:    (a)	Fresh Fish Co./Proof Niteclub at 7800 E. Hampden Ave, Denver, CO 80231:  On and before October 11, 2012, a microwave oven and a dish warmer cart were powered via a temporary extension cord.  This condition exposed the employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0