OSHA Inspection: AIRGAS SPECIALTY PRODUCTS INC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of AIRGAS SPECIALTY PRODUCTS INC in 900 DELAWARE AVENUE, PALMERTON, PA 18071 (NAICS 424690). OSHA activity number 337270219.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Airgas Specialty Products INC — free Get an email when a new federal OSHA severe-injury report for Airgas Specialty Products INC is published. One employer, no account, unsubscribe in one click.
Site address
900 DELAWARE AVENUE
City
PALMERTON
State
PA
ZIP
18071
Mailing
900 DELAWARE AVENUE, PALMERTON, PA 18071
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424690
Employees
9
Ownership type
A

4 citations on file for this inspection.

1910.119 D03 I D

Other-than-serious 1 instance 10 exposed
Issued
May 3, 2013
Abate by
May 3, 2013
Penalty
Initial $3,060 · Current $3,060
29 CFR 1910.119(d)(3)(i)(D):     Information pertaining to the equipment in the process did not include relief system design and design basis:    a.) The employer did not have the relief system design information for the pressure relief valves on the spheres, on or about 4-4-13.    Abatement Observed During Inspection-No certification Required
Recent events (2)
  • — I (O) $3060
  • — Z (S) $3060

1910.119 D03 I B

Other-than-serious 1 instance 10 exposed
Issued
May 3, 2013
Abate by
May 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process:    (a) The piping and instrumentation diagrams identified the isolation valves on the West and East spheres as gate valves (GV162 and GV 47) and car sealed open, when in fact, the gate valves were not car sealed, on or about 4-25-13.    Abatement Observed During Inspection-No certification Required
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.111 B09 V

Serious Gravity 5 2 instances 10 exposed
Issued
May 3, 2013
Penalty
Initial $3,060 · Current $3,060
29 CFR 1910.111 (b)(9)(v):  Shutoff valves shall not be installed between the safety-relief valves and the container; except, that a shut-off valve may be used where the arrangement of this valve is such as always to afford full required capacity flow through the relief valves:   a.) East Sphere- A gate valve was located between the safety-relief valve and the container and no positive means was used to ensure the safety-relief valve remained open, on or about 2-4-13.   b.) West Sphere- A gate valve was located between the safety-relief valve and the container and no positive means was used to ensure the safety-relief valve remained open, on or about 2-4-13.    Abatement Observed During Inspection-No certification Required
Recent events (2)
  • — I (S) $3060
  • — Z (S) $3060

1910.119 F03

Other-than-serious 1 instance 1 exposed
Issued
May 3, 2013
Abate by
Jun 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.119(f)(3): The operating procedures were not reviewed to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities.  (a) The operating procedures do not reflect current operating practice in that the SOP A-36, Sensor Calibration, states that the ammonia test bottle contains 100 ppm; however the ammonia used is 200 ppm, on or about 4-12-13.  (b) The operating procedures do not reflect current operating practice in that the SOP A-36, Sensor Calibration, states the sensor calibration procedures for four sensors that are not in use at the facility, on or about 4-12-13.  Abatement Certification Required
Recent events (2)
  • — I (O) $0
  • — Z (O) $0