Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RICH PRODUCTS CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of RICH PRODUCTS CORPORATION in 2805 SMITH DRIVE, WAYCROSS, GA 31503 (NAICS 311412). OSHA activity number 337289011.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Rich Products Corporation — free Get an email when a new federal OSHA severe-injury report for Rich Products Corporation is published. One employer, no account, unsubscribe in one click.
Site address
2805 SMITH DRIVE
City
WAYCROSS
State
GA
ZIP
31503
Mailing
2805 SMITH DRIVE, WAYCROSS, GA 31503
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311412
Employees
76
Ownership type
A

6 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 2 instances 2 exposed
Issued
Apr 12, 2013
Penalty
Initial $3,300 · Current $1,650 Reduced
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    a) Oven Room - On or about November 7, 2012 and times prior to, a BABBCO electrical enclosure housed exposed live wires that powered the 120-volt actuators for the oven dampers, exposing employees to an electrical shock hazard.      ABATEMENT CERTIFICATION IS NOT REQUIRED
Recent events (2)
  • — I (S) $1650
  • — Z (S) $3300

1910.305 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 12, 2013
Penalty
Initial $4,400 · Current $2,200 Reduced
29 CFR 1910.305(e)(1):     Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:    a) Dough Room, Control Room - On or about November 7, 2012 and times prior to, during the sanitation process, moisture or water could enter an unused opening (knockout) that was not covered on the 460-volt disconnect panel for Dough Mixer #2, exposing employees to an electrical hazard.      ABATEMENT CERTIFICATION IS NOT REQUIRED
Recent events (2)
  • — I (S) $2200
  • — Z (S) $4400

1910.23 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 12, 2013
Penalty
Initial $22,000 · Current $11,000 Reduced
29 CFR 1910.23(c)(1):     Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:    Note:  Toeboards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard.    a) Oven Room - On or about November 7, 2012 and times prior to, the employer did not ensure that employees who accessed the top surface of an industrial sized oven to perform cleaning operations, were protected from potential fall hazards of about 7 feet, 4 inches onto concrete ground due to the elevated work platform being open on all sides.     b) High Pressure Receiver Catwalk (Engine Room #1) - On or about November 8, 2012 and times prior to, the employer did not ensure that employees who accessed the high pressure receiver catwalk for maintenance duties, were protected from potential fall hazards of about 16 feet onto earthen ground due to the elevated work platform having open sides adjacent to the high pressure receiver and adjacent to the condenser catwalk.     ABATEMENT CERTIFICATION IS NOT REQUIRED    Rich Products Corporation was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1910.23(c)(1)], which was contained in OSHA inspection number 314096545, citation number 01, item number 003 and was affirmed as a final order on June 7, 2009, with respect to a workplace located at 200 Glyndale Drive, Brunswick, GA 31520.
Recent events (2)
  • — I (S) $11000
  • — Z (R) $22000

1910.305 G01 IV A

Serious 4 instances 1 exposed
Issued
Apr 12, 2013
Penalty
Initial $5,500 · Current $2,750 Reduced
29 CFR 1910.305(g)(1)(iv)(A):     Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:     a) Chemical Cage, South Wall - On or about November 6, 2012 and times prior to, a flexible cord that was connected into a 120-volt wall mounted junction box was used in lieu of fixed wiring of a structure to energize an overhead fluorescent light, exposing employees to an electrical hazard.      b) Chemical Cage, North Wall - On or about November 6, 2012 and times prior to, a flexible cord that was connected into the same 120-volt wall mounted junction box, was used in lieu of fixed wiring of a structure to energize an overhead fluorescent light, exposing employees to an electrical hazard.      c) Dough Mixing Area Control Room - On or about November 7, 2012 and times prior to, a flexible cord that was connected into a 120-volt wall mounted junction box, was used in lieu of fixed wiring of a structure to energize a water meter, exposing employees to an electrical hazard.      d) Dough Mixing Area  - On or about November 7, 2012 and times prior to, a flexible cord that was connected into a 120-volt wall mounted junction box, was used in lieu of fixed wiring of a structure to energize a floor scale, exposing employees to an electrical hazard.      ABATEMENT CERTIFICATION IS NOT REQUIRED    Rich Products Corporation was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1910.305(g)(1)(iv)(A)], which was contained in OSHA inspection number 314096545, citation number 02, item number 003 and was affirmed as a final order on June 7, 2009 with respect to a workplace located at 200 Glyndale Drive, Brunswick, GA 31520.
Recent events (2)
  • — I (S) $2750
  • — Z (R) $5500

1910.305 G02 II

Other-than-serious 1 instance 2 exposed
Issued
Apr 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii):     Flexible cords were not used in continuous lengths without splice or tap:    a) Chemical Cage, South Wall - On or about November 6, 2012 and times prior to, flexible cords were spliced together to energize an overhead fluorescent light, exposing employees to an electrical hazard.     ABATEMENT CERTIFICATION IS NOT REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 G01

Other-than-serious 1 instance 2 exposed
Issued
Apr 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(g)(1):     The employer did not have a material safety data sheet for each hazardous chemical in use:    a) 2805 Smith Drive - On or about November 6, 2012, the employer did not have a material safety data sheet for chemicals including but not limited to oxygen, acetylene, argon, filler rods and base metal (stainless steel) used for welding operations, exposing employees to possible skin and eye irritations.      ABATEMENT CERTIFICATION IS NOT REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Rich Products Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337289011.