THE DALLES, OR —
OSHA Inspection: ARMY CORPS OF ENGINEERS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ARMY CORPS OF ENGINEERS in THE DALLES DAM, THE DALLES, OR 97058 (NAICS 924110). OSHA activity number 337304612.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARMY CORPS OF ENGINEERS
- Site address
- THE DALLES DAM
- City
- THE DALLES
- State
- OR
- ZIP
- 97058
- Mailing
- P.O. BOX 564, THE DALLES, OR 97058
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924110
- Employees
- 121
- Ownership type
- D
Citations
2 citations on file for this inspection.
1910.305 A02 I
- Issued
- Apr 2, 2013
- Abate by
- Sep 30, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in prohibited manners:Note: Temporary electrical power and lighting installation(s) may only be used as specified by 1910.305(a)(2)(i)(A) through 1910.305(a)(2)(i)(C). (a) Main electrical power to the Safety/Environmental Office has been set-up with a back feed line to the building's main breaker panel and has exceeded the 90 day period.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J02 IV
- Issued
- Apr 2, 2013
- Abate by
- Apr 26, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: (a) Two 110 volt receptacles located in the Rangers lunch room were not equipped with GFCI devices, exposing employees to electrical shocks. One receptacle was directly above the sink and the other was 2 1/2 feet away.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Army Corps of Engineers
View Army Corps of Engineers's full OSHA safety record →
More inspections in this industry (NAICS 924110)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337304612.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.