Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: COMMITMENT 2000 INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of COMMITMENT 2000 INC in 105 MONSIGNOR VALENTE DRIVE, BUFFALO, NY 14206 (NAICS 311812). OSHA activity number 337349815.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Commitment 2000 INC — free Get an email when a new federal OSHA severe-injury report for Commitment 2000 INC is published. One employer, no account, unsubscribe in one click.
Establishment
COMMITMENT 2000 INC
Site address
105 MONSIGNOR VALENTE DRIVE
City
BUFFALO
State
NY
ZIP
14206
Mailing
105 MONSIGNOR VALENTE DRIVE, BUFFALO, NY 14206
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311812
Employees
45
Ownership type
A

5 citations on file for this inspection.

1910.37 A03

Serious Gravity 1 1 instance 4 exposed
Issued
Jan 11, 2013
Abate by
Feb 15, 2013
Penalty
Initial $1,785 · Current $1,339 Reduced
29 CFR 1910.37(a)(3):     Exit route(s) were not kept free and unobstructed:    a) On or about 11/14/12, in the forklift traffic area wall markings 28 and 29, an exit route/door access was blocked by a Wright Self Dumping Hopper.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1338.75
  • — Z (S) $1785

1910.147 C01

Serious Gravity 5 1 instance 4 exposed
Issued
Jan 11, 2013
Abate by
Feb 15, 2013
Penalty
Initial $2,975 · Current $2,231 Reduced
29 CFR 1910.147(c)(1):     The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:    a) On or about 11/14/12, in the establishment, employees are involved in servicing and maintaining equipment, such as, but not limited to: repairing a I.J. Whithe Cooler Conveyor's chain, changing a Press belt and cleaning a T-line Mixer, without using an energy control program, machine-specific/group lockout-tagout procedures, hardware, training or periodic inspections.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $2231.25
  • — Z (S) $2975

1910.151 C

Serious Gravity 5 1 instance 5 exposed
Issued
Jan 11, 2013
Abate by
Feb 15, 2013
Penalty
Initial $2,380 · Current $1,785 Reduced
29 CFR 1910.151(c):     Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:      a) On or about 11/14/12, in the chemical room, there was not an Emergency Eye wash immediately available for sanitation employees handling and transferring corrosive chemicals such as, but not limited to: PE-12, Heavy Duty Commercial Cleaner and Sanitime.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2380

1910.212 A03 II

Serious Gravity 5 1 instance 4 exposed
Issued
Jan 11, 2013
Penalty
Initial $2,380 · Current $1,785 Reduced
29 CFR 1910.212(a)(3)(ii):     Point of operation guards were not designed and constructed as to prevent the operator from having any part of their body in the danger zone during the operating cycle:    a) On or about 11/14/12, in the A-Line production areas, an Empire Mixer had an inadequate guard with openings of approximately 4 inches exposing employees' hands/fingers to be in contact with mixer's agitator.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2380

1910.303 G01

Other-than-serious 1 instance 2 exposed
Issued
Jan 11, 2013
Abate by
Feb 15, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1):     Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:      a) On or about 11/04/12, in the production areas, electrical panels and a disconnect switch access were blocked by a yellow plastic container, Igloo water container and a garbage container.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Commitment 2000 INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337349815.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.