Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ARMY CORPS OF ENGINEERS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ARMY CORPS OF ENGINEERS in THE DALLES DAM, THE DALLES, OR 97058 (NAICS 221122). OSHA activity number 337410823.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Army Corps of Engineers — free Get an email when a new federal OSHA severe-injury report for Army Corps of Engineers is published. One employer, no account, unsubscribe in one click.
Site address
THE DALLES DAM
City
THE DALLES
State
OR
ZIP
97058
Mailing
P.O. BOX 564, THE DALLES, OR 97058
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
121
Ownership type
D

4 citations on file for this inspection.

1910.212 B

Serious Gravity 5 1 instance 47 exposed
Issued
Apr 2, 2013
Abate by
Apr 26, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:    (a) The Baldor pedestal grinder, located in the Power House 5th floor area, was not anchored to the floor.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 C03

Serious Gravity 5 2 instances 75 exposed
Issued
Apr 2, 2013
Abate by
Jun 13, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.219(c)(3): Vertical or inclined shafting seven feet or less from floor or working platform was not enclosed with stationary casing(s)    Station Service Turbine #2-  (a) The inspection revealed that the employer did not provide adequate warning signs and/or barriers to keep unqualified personnel (e.g. private contractors) away from rotating vertical shafts.    Station Service Turbine #1-  (a) The inspection revealed that the employer did not provide adequate warning signs and/or barriers to keep unqualified personnel (e.g. private contractors) away from rotating vertical shafts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 A02 I

Serious Gravity 10 1 instance 3 exposed
Issued
Apr 2, 2013
Abate by
Apr 26, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.269(a)(2)(i): Employees were not trained in nor were they familiar with the safety-related work practices, safety procedures, and other safety requirements that pertained to their respective job assignments:    Powerhouse 5th floor, Bay 1-  (a) Employees involved in the switching evolution on or about July 17, 2012 were exposed to serious injuries when an Arc Flash incident occurred.  The switching order was incorrect and allowed a switch to be in an energized state and under a load as a trainee was operating a crank to open the disconnect when 201 kW/10 amps of energy was released.    Note: Abatement certification and supporting documentation are required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J01 I

Serious Gravity 5 2 instances 50 exposed
Issued
Apr 2, 2013
Abate by
Apr 26, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact:     Between Bay 10 and 11-  (a) The light fixture 6 feet, 5 inches from the floor, was missing the bulb and had exposed live parts.     Power House 5th floor-  (b) The Baldor pedestal grinder's light fixture, located 30" above the floor, exposed live parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Army Corps of Engineers's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337410823.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.