OSHA Inspection: GERALD GRAIN CENTER, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GERALD GRAIN CENTER, INC in 3265 CO. RD. 24, ARCHBOLD, OH 43502 (NAICS 424510). OSHA activity number 337600019.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gerald Grain Center, INC — free Get an email when a new federal OSHA severe-injury report for Gerald Grain Center, INC is published. One employer, no account, unsubscribe in one click.
Site address
3265 CO. RD. 24
City
ARCHBOLD
State
OH
ZIP
43502
Mailing
3265 CO. RD. 24, ARCHBOLD, OH 43502
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
17
Ownership type
A

9 citations on file for this inspection.

1910.134 E01

Other-than-serious 1 instance 5 exposed
Issued
Mar 12, 2013
Abate by
Mar 29, 2013
Penalty
Initial $1,890 · Current $0 Reduced
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about November 29, 2012, the employer failed to provide medical evaluations to those employees who voluntarily wore half mask tight-fitting respirators while working in the mill warehouse. Employees were exposed to hazards from aggravation of pulmonary issues while wearing the respirators without medical clearance.
Recent events (2)
  • — I (O) $0
  • — Z (S) $1890

1910.332 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 12, 2013
Abate by
Mar 28, 2013
Penalty
Initial $4,410 · Current $4,410
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 15, 2012, the employer failed to ensure that employees who worked on 480V electrical equipment were provided with adequate training for qualified persons on protective equipment for the face, hands, and body as well as requirements for verifying a zero energy state to protect against electric shock and arc flash hazards.
Recent events (2)
  • — I (S) $4410
  • — Z (S) $4410

1910.333 A

Serious Gravity 10 2 instances 1 exposed
Issued
Mar 12, 2013
Abate by
Mar 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 15, 2012, the employer failed to ensure that employees used electrical safety related work practices when changing out a fuse in a 480V electrical cabinet for the NW Feed Auger, in that proper PPE was not worn and zero energy was not verified. Employees were exposed to electrical shock and arc flash hazards.    b) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 20, 2012, the employer failed to ensure that employees used electrical safety related work practices when changing out 3 heaters in a 480V electrical cabinet for the NW Feed Auger, in that proper PPE was not worn and zero energy was not verified. Employees were exposed to electrical shock and arc flash hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 IV B

Serious Gravity 10 2 instances 1 exposed
Issued
Mar 12, 2013
Abate by
Mar 28, 2013
Penalty
Initial $4,410 · Current $0 Reduced
29 CFR 1910.333(b)(2)(iv)(B): A qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that it was deenergized:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 15, 2012, the employer failed to ensure that employees verified zero energy when changing out a fuse in a 480V electrical cabinet for the NW Feed Auger, which exposed employees to electrical shock and arc flash hazards.    b) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 20, 2012, the employer failed to ensure that employees verified zero energy when changing out 3 heaters in a 480V electrical cabinet for the NW Feed Auger, which exposed employees to electrical shock and arc flash hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4410

1910.333 B02 III A

Deleted Serious Gravity 10 2 instances 1 exposed
Issued
Mar 12, 2013
Abate by
Mar 29, 2013
Penalty
Initial $4,410 · Current $0 Reduced
29 CFR 1910.333(b)(2)(iii)(A): A lock and a tag were not placed on each disconnecting means used to deenergize circuits and equipment on which work was to be performed:      a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 15, 2012, the employer failed to ensure that employees placed a lock and/or tag on an electrical cabinet. Employees were exposed to electrical shock and arc flash hazards while changing out a fuse in a 480V electrical cabinet for the NW Feed Auger.    b) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 20, 2012, the employer failed to ensure that employees placed a lock and/or tag on an electrical cabinet. Employees were exposed to electrical shock and arc flash hazards while changing out 3 heaters in a 480V electrical cabinet for the NW Feed Auger.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4410

1910.335 A01 I

Serious Gravity 10 2 instances 1 exposed
Issued
Mar 12, 2013
Abate by
Mar 29, 2013
Penalty
Initial $4,410 · Current $4,410
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 15, 2012, the employer failed to ensure that employees wore personal protective equipment including but not limited to, insulated gloves with leather gloves and arc rated clothing while changing out a fuse in a 480V electrical cabinet for the NW Feed Auger, exposing employees to electrical shock and arc flash hazards.    b) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 20, 2012, the employer failed to ensure that employees wore personal protective equipment including but not limited to, insulated gloves with leather gloves and arc rated clothing while changing out 3 heaters in a 480V electrical cabinet for the NW Feed Auger, exposing employees to electrical shock and arc flash hazards.
Recent events (2)
  • — I (S) $4410
  • — Z (S) $4410

1910.335 A01 IV

Serious Gravity 10 2 instances 1 exposed
Issued
Mar 12, 2013
Abate by
Mar 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(iv): Employees did not wear nonconductive head protection wherever there was a danger of head injury from electric shock or burns due to contact with exposed energized parts:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 15, 2012, the employer failed to ensure that employees wore nonconductive head protection while changing out a fuse in a 480V electrical cabinet for the NW Feed Auger, exposing employees to electrical shock and arc flash hazards.    b) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 20, 2012, the employer failed to ensure that employees wore nonconductive head protection while changing out 3 heaters in a 480V electrical cabinet for the NW Feed Auger, exposing employees to electrical shock and arc flash hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 V

Serious Gravity 10 2 instances 1 exposed
Issued
Mar 12, 2013
Abate by
Mar 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v): Employees did not wear protective equipment for the eyes or face wherever there was danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 15, 2012, the employer failed to ensure that employees wore an arc rated face shield while changing out a fuse in a 480V electrical cabinet for the NW Feed Auger, exposing employees to electrical shock and arc flash hazards.    b) Gerald Grain Center, Inc. - Archbold, Ohio: On or about September 20, 2012, the employer failed to ensure that employees wore an arc rated face shield while changing out 3 heaters in a 480V electrical cabinet for the NW Feed Auger, exposing employees to electrical shock and arc flash hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 D03 II

Other-than-serious 1 instance 5 exposed
Issued
Mar 12, 2013
Abate by
Mar 22, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.134(d)(3)(ii): The employer did not provide a respirator that was appropriate for the chemical state and physical form of the contaminant:    a) Gerald Grain Center, Inc. - Archbold, Ohio: On or about November 29, 2012, the employer failed to select the correct cartridges for use with a half-mask tightfitting respirator in the mill warehouse area. Employees wore NIOSH approved cartridges for organic vapors instead of HEPA filters for protection against dust.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Gerald Grain Center, INC's full OSHA safety record →