WEST MEMPHIS, AR —
OSHA Inspection: NGL SUPPLY TERMINAL, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NGL SUPPLY TERMINAL, LLC in 1241 S. 8TH STREET, WEST MEMPHIS, AR 72303 (NAICS 424710). OSHA activity number 337828628.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NGL SUPPLY TERMINAL, LLC
- Site address
- 1241 S. 8TH STREET
- City
- WEST MEMPHIS
- State
- AR
- ZIP
- 72303
- Mailing
- 6120 S. YALE AVE, TULSA, OK 74136
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424710
- Employees
- 3
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.119 D03 II
- Issued
- Feb 25, 2013
- Abate by
- Dec 2, 2013
- Penalty
- Initial $4,900 · Current $4,000 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices. The employer does not ensure it documented that equipment in the process complied with recognized and generally accepted good engineering practices. a. The violation occurred in the West Memphis Terminal facility where the employer failed to document bulk liquid hydrocarbon storage vessels complied with recognized and generally accepted good engineering practices such as API 510. Identified vessels include but are not limited to VST-2300, VST-2310, VST-2260, VST-2270, VST-2280, VST-2370, and VST-2390. This condition exposed employees to fire and explosion hazards. b. The violation occurred in the West Memphis Terminal facility where the employer failed to document bulk liquid hydrocarbon storage piping complied with recognized and generally accepted good engineering practices such as API 570. Identified piping includes but is not limited to piping from the bulk hydrocarbon storage vessels to the pumps. This condition exposed employees to fire and explosion hazards. Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure it documents that equipment in the process complies with recognized and generally accepted good engineering practices.
Recent events (2)
- — I (S) $4000
- — Z (S) $4900
1910.119 J02
- Issued
- Feb 25, 2013
- Abate by
- Dec 2, 2013
- Penalty
- Initial $4,900 · Current $4,000 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going mechanical integrity of process equipment. The employer does not ensure written procedures are established and implemented to maintain the on-going mechanical integrity of process equipment. a. The violation occurred in the West Memphis Terminal facility where the employer failed to ensure detailed written procedures were established and implemented for determining locations for conducting thickness measurements for piping and bulk liquid hydrocarbon storage vessels. This condition exposed employees to fire, and explosion hazards. b. The violation occurred in the West Memphis Terminal facility where the employer failed to ensure detailed written procedures were established and implemented for performing visual external inspections of piping and vessels. This condition exposed employees to fire and explosion hazards. c. The violation occurred in the West Memphis Terminal facility where the employer failed to ensure detailed written procedures were established and implemented for testing of safeguards. Identified safeguards include but are not limited to the emergency shutdown and deluge systems. This condition exposed employees to fire and explosion hazards. Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure written procedures are established and implemented to maintain the on-going mechanical integrity of process equipment.
Recent events (2)
- — I (S) $4000
- — Z (S) $4900
1910.119 J04 II
- Issued
- Feb 25, 2013
- Abate by
- Dec 2, 2013
- Penalty
- Initial $4,900 · Current $4,000 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(ii): Inspections and testing procedures performed on process equipment to maintain its mechanical integrity, did not follow recognized and generally accepted good engineering practices. The employer does not ensure inspections and tests performed on process equipment to maintain its on-going mechanical integrity followed recognized and generally accepted good engineering practices. a. The violation occurred in the West Memphis Terminal facility where the employer failed to ensure inspections and tests of bulk liquid hydrocarbon storage vessels followed recognized and generally accepted good engineering practices such as API 510. Identified vessels include but are not limited to VST-2300, VST-2310, VST-2260, VST-2270, VST-2280, VST-2370, and VST-2390. This condition exposed employees to fire and explosion hazards. b. The violation occurred in the West Memphis Terminal facility where the employer failed to ensure inspections and tests of bulk liquid hydrocarbon storage piping followed recognized and generally accepted good engineering practices such as API 570. Identified piping includes but is not limited to piping from the bulk hydrocarbon storage vessels to the pumps. This condition exposed employees to fire and explosion hazards. Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure inspections and tests performed on process equipment to maintain its on-going mechanical integrity followed recognized and generally accepted good engineering practices.
Recent events (2)
- — I (S) $4000
- — Z (S) $4900
More inspections at NGL Supply Terminal, LLC
View NGL Supply Terminal, LLC's full OSHA safety record →
More inspections in this industry (NAICS 424710)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337828628.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.