OSHA Inspection: NGL SUPPLY TERMINAL, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NGL SUPPLY TERMINAL, LLC in 4580 HIGHWAY 189 NORTH, KINGSLAND, AR 71652 (NAICS 424710). OSHA activity number 339574204.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NGL Supply Terminal, LLC — free Get an email when a new federal OSHA severe-injury report for NGL Supply Terminal, LLC is published. One employer, no account, unsubscribe in one click.
Site address
4580 HIGHWAY 189 NORTH
City
KINGSLAND
State
AR
ZIP
71652
Mailing
6120 S. YALE AVE, TULSA, OK 74136
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424710
Employees
1
Ownership type
A

3 citations on file for this inspection.

1910.119 F01 II

Other-than-serious 3 instances 1 exposed
Issued
May 8, 2014
Abate by
Jun 23, 2014
Penalty
Initial $3,500 · Current $1,000 Reduced
29 CFR 1910.119(f)(1)(ii):  The employer's written operating procedures did not address the consequences of and the steps required for correcting or avoiding deviation from the operating limits.         The employer does not ensure written operating procedures addressed steps required for correcting or avoiding deviations from the safe upper and lower limits of the process.       The violation occurred on or about February 5, 2014 and at times prior thereto in the propane terminal areas where the employer failed to ensure written operating procedures addressed the steps required for correcting or avoiding deviations from the safe upper and lower limits of the process. Identified operating limits include but not limited to:    a.     High/Low liquid level   b.     High/Low pressure limits   c.     High/Low Flow Rates      This condition exposed employees to fire and explosion hazards.      Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure written operating procedures addressed the steps required for correcting or avoiding deviations from the safe upper and lower limits of the process.
Recent events (2)
  • — I (O) $1000
  • — Z (S) $3500

1910.119 D03 II

Repeat Gravity 5 2 instances 1 exposed
Issued
May 8, 2014
Abate by
Jun 23, 2014
Penalty
Initial $7,000 · Current $6,000 Reduced
29 CFR 1910.119(d)(3)(ii):  The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices:         The employer does not ensure it documented that equipment in the process complied with recognized and generally accepted good engineering practices.       a.     The violation occurred on or about February 5, 2014 and at times prior thereto in the propane terminal where the employer failed to document bulk liquid hydrocarbon storage vessels complied with recognized and generally accepted good engineering practices such as ASME Section VIII and API 510. Identified vessels include but are not limited to VST-2100, VST-2140, VST-2150, and VST-2160.  This condition exposed employees to fire and explosion hazards.       b.     The violation occurred on or about February 5, 2014 and at times prior thereto in the propane terminal where the employer failed to document bulk liquid hydrocarbon storage piping complied with recognized and generally accepted good engineering practices such as ASME Section B31 and API 570. Identified piping includes but is not limited to piping from the bulk hydrocarbon storage vessels to the truck loading facility. This condition exposed employees to fire and explosion hazards.       NGL SUPPLY TERMINAL, LLC WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIPVALENT STANDARD, 29 CFR 1910.119(d)(3)(ii), WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER #782862, CITATION NUMBER #1, Item# 1 AND WAS AFFIRMED AS FINAL ORDER ON MARCH 26, 2013 WITH RESPECT TO A WORKPLACE LOCATED AT WEST MEMPHIS TERMINAL 1282 S 8TH STREET, WEST MEMPHIS AR 73201.    Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure it documents that equipment in the process complies with recognized and generally accepted good engineering practices.
Recent events (2)
  • — I (R) $6000
  • — Z (R) $7000

1910.119 J04 II

Repeat Gravity 5 2 instances 1 exposed
Issued
May 8, 2014
Abate by
Jun 23, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.119(j)(4)(ii):  Inspections and testing procedures performed on process equipment to maintain its mechanical integrity, did not follow recognized and generally accepted good engineering practices.     The employer does not ensure inspections and tests performed on process equipment to maintain its on-going mechanical integrity followed recognized and generally accepted good engineering practices.       a.     The violation occurred on or about February 5, 2014 and at times prior thereto in the propane terminal where the employer failed ensure inspections and tests of bulk liquid hydrocarbon storage pressure vessels followed recognized and generally accepted good engineering practices such as API 510. Identified vessels include but are not limited to VST-2100, VST-2140, and VST-2150.  This condition exposed employees to fire and explosion hazards.       b.     The violation occurred on or about February 5, 2014 and at times prior thereto in the propane terminal where the employer failed ensure inspections and tests of terminal hydrocarbon piping followed recognized and generally accepted good engineering practices such as API 570. Identified piping includes but is not limited to hydrocarbon in the terminal from the storage vessels to the truck loading facility. This condition exposed employees to fire and explosion hazards.       NGL SUPPLY TERMINAL, LLC WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIPVALENT STANDARD, 29 CFR 1910.119(j)(4)(ii), WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER #782862, CITATION NUMBER #1, Item# 3 AND WAS AFFIRMED AS FINAL ORDER ON MARCH 26, 2013 WITH RESPECT TO A WORKPLACE LOCATED AT WEST MEMPHIS TERMINAL 1282 S 8TH STREET, WEST MEMPHIS AR 73201.    Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure inspections and tests performed on process equipment to maintain its on-going mechanical integrity followed recognized and generally accepted good engineering practices.