SIDNEY, OH —
OSHA Inspection: MAMA ROSA'S, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MAMA ROSA'S, LLC in 1910 FAIR RD., SIDNEY, OH 45365 (NAICS 311412). OSHA activity number 337981229.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAMA ROSA'S, LLC
- Site address
- 1910 FAIR RD.
- City
- SIDNEY
- State
- OH
- ZIP
- 45365
- Mailing
- 1910 FAIR RD., SIDNEY, OH 45365
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311412
- Employees
- 290
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.212 A01
- Issued
- Feb 6, 2013
- Abate by
- Feb 15, 2013
- Penalty
- Initial $4,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a) Mama Rosa's, LLC, Sidney, Ohio: On or about December 20, 2012, the employer did not ensure that employees were protected from caught-by hazards while using the Bridgeport Machines, Inc. manufactured milling machine. Employees used the machine with an unguarded rotating chuck to perform work on various items. b) Mama Rosa's, LLC, Sidney, Ohio: On or about November 8, 2012, the employer did not ensure that employees were protected from caught-by hazards while using the Dayton manufactured 20 Drill Press. Employees used the machine with an unguarded rotating chuck to perform work on various items.
Recent events (2)
- — I (S) $3500
- — Z (S) $4000
1910.332 B01
- Issued
- Feb 6, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $7,000 · Current $6,500 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) Mama Rosa's, LLC, Sidney, Ohio: On or about December 20, 2012, the employer did not ensure that employees were provided with training on electrical safety-related work practices, such as but not limited to electrical shock hazards, arc flash/blast hazards, proper verification techniques and protective equipment for the face, head and hands to protect against electrical hazards while working on or near energized or potentially energized conductors. Employees engaged in fuse changing activities along with general electrical service/repair did not utilize electrical safety-related work practices.
Recent events (2)
- — I (S) $6500
- — Z (S) $7000
1910.333 A
- Issued
- Feb 6, 2013
- Abate by
- Feb 26, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: a) Mama Rosa's, LLC, Sidney, Ohio: On or about December 20, 2012, the employer did not ensure that electrical safety-related work practices were employed to prevent electrical shock or other injuries when employees were performing maintenance operations on electrical systems.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Feb 6, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a) Mama Rosa's, LLC, Sidney, Ohio: On or about December 19, 2012, the employer failed to ensure that employees were protected from electrical hazards in that electrical protective equipment for the hands were not required to be used by employees who accessed potentially live electrical panels. The employees were exposed to 480 volts while testing fuses and verifying power to the electrical equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.335 A01 IV
- Issued
- Feb 6, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not wear nonconductive head protection: a) Mama Rosa's, LLC, Sidney, Ohio: On or about December 19, 2012, the employer failed to ensure that employees were protected from electrical hazards in that nonconductive head protection was not required to be worn by employees who accessed potentially live electrical panels. Employees were exposed to 480 volts while testing fuses and verifying power to electrical equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 V
- Issued
- Feb 6, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face: a) Mama Rosa's, LLC, Sidney, Ohio: On or about February 9, 2012, the employer failed to ensure that employees were protected from electrical hazards in that nonconductive face protection was not used by employees who accessed potentially live electrical panels. Employees were exposed to 480 volts while testing fuses and verifying power to electrical equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 II
- Issued
- Feb 6, 2013
- Abate by
- Feb 19, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(ii): Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested: a) Mama Rosa's, LLC, Sidney, Ohio: On or about December 20, 2012, the employer failed to ensure that rubber insulating gloves provided to employees were periodically inspected as required. One pair of gloves had a test date stamp of May 2004 and a second pair had test date stamp of April 2006. Both pairs of gloves were available for employee use when they were engaged in electrical service/repair work.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Mama Rosa'S, LLC
View Mama Rosa'S, LLC's full OSHA safety record →
More inspections in this industry (NAICS 311412)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337981229.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.