Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MAMA ROSA'S, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MAMA ROSA'S, LLC in 1910 FAIR RD., SIDNEY, OH 45365 (NAICS 311412). OSHA activity number 337981229.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mama Rosa'S, LLC — free Get an email when a new federal OSHA severe-injury report for Mama Rosa'S, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
MAMA ROSA'S, LLC
Site address
1910 FAIR RD.
City
SIDNEY
State
OH
ZIP
45365
Mailing
1910 FAIR RD., SIDNEY, OH 45365
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311412
Employees
290
Ownership type
A

7 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 2 instances 1 exposed
Issued
Feb 6, 2013
Abate by
Feb 15, 2013
Penalty
Initial $4,000 · Current $3,500 Reduced
29 CFR 1910.212(a)(1):  One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    a)  Mama Rosa's, LLC, Sidney, Ohio:  On or about December 20, 2012, the employer did not ensure that employees were protected from caught-by hazards while using the Bridgeport Machines, Inc. manufactured milling machine.  Employees used the machine with an unguarded rotating chuck to perform work on various items.    b)  Mama Rosa's, LLC, Sidney, Ohio:  On or about November 8, 2012, the employer did not ensure that employees were protected from caught-by hazards while using the Dayton manufactured 20 Drill Press.  Employees used the machine with an unguarded rotating chuck to perform work on various items.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $4000

1910.332 B01

Serious Gravity 10 1 instance 3 exposed
Issued
Feb 6, 2013
Abate by
Feb 25, 2013
Penalty
Initial $7,000 · Current $6,500 Reduced
29 CFR 1910.332(b)(1):  Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    a) Mama Rosa's, LLC, Sidney, Ohio:  On or about December 20, 2012, the employer did not ensure that employees were provided with training on electrical safety-related work practices, such as but not limited to electrical shock hazards, arc flash/blast hazards, proper verification techniques and protective equipment for the face, head and hands to protect against electrical hazards while working on or near energized or potentially energized conductors.  Employees engaged in fuse changing activities along with general electrical service/repair did not utilize electrical safety-related work practices.
Recent events (2)
  • — I (S) $6500
  • — Z (S) $7000

1910.333 A

Serious Gravity 10 1 instance 3 exposed
Issued
Feb 6, 2013
Abate by
Feb 26, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a):  Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:    a) Mama Rosa's, LLC, Sidney, Ohio:  On or about December 20, 2012, the employer did not ensure that electrical safety-related work practices were employed to prevent electrical shock or other injuries when employees were performing maintenance operations on electrical systems.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 3 exposed
Issued
Feb 6, 2013
Abate by
Feb 25, 2013
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.335(a)(1)(i):  Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    a) Mama Rosa's, LLC, Sidney, Ohio:  On or about December 19, 2012, the employer failed to ensure that employees were protected from electrical hazards in that electrical protective equipment for the hands were not required to be used by employees who accessed potentially live electrical panels.  The employees were exposed to 480 volts while testing fuses and verifying power to the electrical equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.335 A01 IV

Serious Gravity 10 1 instance 3 exposed
Issued
Feb 6, 2013
Abate by
Feb 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(iv):  Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not wear nonconductive head protection:    a) Mama Rosa's, LLC, Sidney, Ohio:  On or about December 19, 2012, the employer failed to ensure that employees were protected from electrical hazards in that nonconductive head protection was not required to be worn by employees who accessed potentially live electrical panels.  Employees were exposed to 480 volts while testing fuses and verifying power to electrical equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 V

Serious Gravity 10 1 instance 3 exposed
Issued
Feb 6, 2013
Abate by
Feb 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v):  Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:    a) Mama Rosa's, LLC, Sidney, Ohio:  On or about February 9, 2012, the employer failed to ensure that employees were protected from electrical hazards in that nonconductive face protection was not used by employees who accessed potentially live electrical panels.  Employees were exposed to 480 volts while testing fuses and verifying power to electrical equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 II

Other-than-serious 1 instance 3 exposed
Issued
Feb 6, 2013
Abate by
Feb 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(ii):  Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested:    a) Mama Rosa's, LLC, Sidney, Ohio:  On or about December 20, 2012, the employer failed to ensure that rubber insulating gloves provided to employees were periodically inspected as required.  One pair of gloves had a test date stamp of May 2004 and a second pair had test date stamp of April 2006.  Both pairs of gloves were available for employee use when they were engaged in electrical service/repair work.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Mama Rosa'S, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337981229.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.