Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ARMY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ARMY in BUILDING 3567 3567 NEELY ROAD, FORT WAINWRIGHT, AK 99703 (NAICS 493110). OSHA activity number 338248610.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Army — free Get an email when a new federal OSHA severe-injury report for Army is published. One employer, no account, unsubscribe in one click.
Establishment
ARMY
Site address
BUILDING 3567 3567 NEELY ROAD
City
FORT WAINWRIGHT
State
AK
ZIP
99703
Mailing
1060 GAFFNEY ROAD MS #7400, FORT WAINWRIGHT, AK 99703
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
23
Ownership type
D

7 citations on file for this inspection.

1910.22 D01

Serious Gravity 1 1 instance 12 exposed
Issued
Jan 29, 2013
Abate by
Feb 27, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1):     On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate.    Warehouse: On or about 9 January 2013 and times prior thereto, the interior storage shelves did not have maximum safe load limits conspicuously placed in each space which they relate. This condition exposed employees to a struck by hazard.
Recent events (1)
  • — Z (S) $0

1910.36 G02

Serious Gravity 1 1 instance 12 exposed
Issued
Jan 29, 2013
Abate by
Feb 27, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2):     Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.    Installation Medical Supply activity warehouse: On or about 9 January 2013 and times prior thereto, the emergemcy exit door, located at the old side of the warehouse, measured 22 inches wide. This condition exposed employees to delays in exiting the building; smoke inhalation, fire, and tripping hazards.
Recent events (1)
  • — Z (S) $0

1910.37 A03

Serious Gravity 1 1 instance 12 exposed
Issued
Jan 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3):     Exit route(s) were not kept free and unobstructed.    Warehouse Refrigerator area: On or about 9 January 2013 and times prior thereto, emergency exits were not kept clear. Refrigerator units were stored in emergency exit path. This condition exposed employees to delays in exiting the building, smoke inhalation, fire, and tripping hazards.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 1 1 instance 12 exposed
Issued
Jan 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):     Each exit was not clearly visible and marked by a sign reading "Exit".    Warehouse Northeast corner: On or about 9 January 2013 and times prior thereto, emergency exit signs were not clearly visible. Exit sign positioning was not clearly visible due to relocation of storage shelves. This condition exposed employees to delays in exiting the building. Smoke inhalation and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.176 A

Serious Gravity 1 1 instance 12 exposed
Issued
Jan 29, 2013
Abate by
May 27, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.176(a):     Where mechanical handling equipment was used, sufficient safe clearances were not allowed for aisles, at loading docks, through doorways or wherever turns or passage had to be made.    Warehouse ramp loading area. On or about 9 January 2013 and times prior thereto, the employer did not ensure that the loading ramp was adequately guarded or marked indicating when approaching the edge. This condition exposes employees to a caught between or under hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.176 B

Serious 1 instance 12 exposed
Issued
Jan 29, 2013
Abate by
May 27, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.176(b):     Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse.    Warehouse: On or about 9 January 2013 and times prior thereto, warehouse storage racks were not secure to floor or walls. This condition exposed employees to a struck by hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 12 exposed
Issued
Jan 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.    Warehouse Refrigerator area: On or about 9 January 2013 and times prior thereto, electrical power strips were not being used as listed or labeled. Cords were daisy chained together. This condition exposed employees to an electrical fire hazard.
Recent events (1)
  • — Z (S) $0

View Army's full OSHA safety record →