Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GARELICK FARMS, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of GARELICK FARMS, LLC in 626 LYNNWAY, LYNN, MA 01902 (NAICS 311511). OSHA activity number 338433634.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Garelick Farms, LLC — free Get an email when a new federal OSHA severe-injury report for Garelick Farms, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
GARELICK FARMS, LLC
Site address
626 LYNNWAY
City
LYNN
State
MA
ZIP
01902
Mailing
626 LYNNWAY, LYNN, MA 01901
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311511
Employees
247
Ownership type
A

7 citations on file for this inspection.

1910.147 C06 I

Serious Gravity 1 1 instance 4 exposed
Issued
Feb 21, 2013
Abate by
Mar 12, 2013
Penalty
Initial $2,525 · Current $1,515 Reduced
29 CFR 1910.147(c)(6)(i):     The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed.    (a) Location - 626 Lynnway, Lynn, MA 01901:    On or about 1/24/2013, the employer failed to ensure that written lock out tag out procedures were evaluated for effectiveness at least annually.
Recent events (2)
  • — I (S) $1515
  • — Z (S) $2525

1910.333 A

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 21, 2013
Abate by
Mar 12, 2013
Penalty
Initial $6,930 · Current $4,160 Reduced
29 CFR 1910.333(a):     Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized.    (a) Location - 626 Lynnway, Lynn, MA 01902:      On or about 1/24/2013, the employer failed to ensure electrical safe working practices were utilized by electricians when performing live work.
Recent events (2)
  • — I (S) $4160
  • — Z (S) $6930

1910.333 A02

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 21, 2013
Abate by
Mar 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(2):     Where exposed live parts were not deenergized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved:    (a) Location - 626 Lynnway, Lynn MA:    On or about 1/24/2013, the employer failed to ensure that employees were protected from electrical hazards while working on live equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 21, 2013
Abate by
Mar 12, 2013
Penalty
Initial $6,930 · Current $4,196 Reduced
29 CFR 1910.335(a)(1):      Employees working in areas where there were potential electrical hazards were not provided with, and/or did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed.    (a) Location - 626 Lynnway, Lynn, MA:     On or about 1/24/2013, the employer failed to ensure that employees performing maintenance tasks on or near live electrical equipment were provided with the appropriate personal protective equipment.
Recent events (2)
  • — I (S) $4196
  • — Z (S) $6930

1910.137 B02 VIII

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 21, 2013
Abate by
Mar 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.137(b)(2)(viii):     Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6.    (a) Location - 626 Lynnway, Lynn, MA 01902:     On or about 1/24/2013, the employer failed to ensure that rubber insulated gloves used by electricians were tested every six months.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 B01

Serious Gravity 1 4 instances 247 exposed
Issued
Feb 21, 2013
Abate by
Mar 12, 2013
Penalty
Initial $2,525 · Current $1,515 Reduced
29 CFR 1910.335(b)(1):     Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them as required by 29 CFR 1910.145.     (a) Location - 626 Lynnway, Lynn, MA 01902:    On or about 1/24/2013, the employer failed to ensure that employees were appropriately warned of electrical hazards  present during infrared testing.
Recent events (2)
  • — I (S) $1515
  • — Z (S) $2525

1910.22 A02

Deleted Other-than-serious 1 instance 4 exposed
Issued
Feb 21, 2013
Abate by
Mar 12, 2013
Penalty
Initial $842 · Current $0 Reduced
29 CFR 1910.22(a)(2):     Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition.    (a) Location - 626 Lynnway, Lynn, MA:    On or about 1/24/2013, the employer failed to ensure that the floor of the filler room was maintained in a dry condition.
Recent events (2)
  • — I (O) $0
  • — Z (O) $842

View Garelick Farms, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338433634.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.