BURLINGTON, NJ —
OSHA Inspection: GARELICK FARMS, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of GARELICK FARMS, LLC in 117 CUMBERLAND BLVD, BURLINGTON, NJ 08016 (NAICS 311511). OSHA activity number 340111095.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GARELICK FARMS, LLC
- Site address
- 117 CUMBERLAND BLVD
- City
- BURLINGTON
- State
- NJ
- ZIP
- 08016
- Mailing
- 117 CUMBERLAND BLVD, BURLINGTON, NJ 08016
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311511
- Employees
- 225
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.37 A03
- Issued
- May 11, 2015
- Abate by
- Jun 5, 2015
- Penalty
- Initial $4,500 · Current $4,650
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) Roof: Exit routes were not kept free and unobstructed. Employees had to travel over pipe chases to access exit routes, on or about 11/17/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (O) $4650
- — C (S) $4500
- — Z (S) $4500
1910.36 G02
- Issued
- May 11, 2015
- Abate by
- Jun 26, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. a)Cooler door 26: The exit route to emergency exit door 26 had limited openings measuring 18 inches between a motor guard and stored stock metal and 24 inches between a motor guard and the door, on or about 11/17/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (O) $0
- — C (S) $0
- — Z (S) $0
1910.119 D03 II
- Issued
- May 11, 2015
- Penalty
- Initial $4,500 · Current $4,650
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. a)Roof: Ammonia pressure relief valves did not discharge to a height at least 15 feet above the adjacent grade. Employer did not document that the ammonia relief complied with RAGAGEP such as but not limited to IIAR-2 section 11.3.6.4, which states "The discharge from pressure relief devices to the atmosphere shall be not less than 15 feet [4.8 m] above the adjacent grade or roof level or as specified by the jurisdictional authority and shall be arranged to avoid spraying of refrigerant on persons in the vicinity." on or about 11/17/14. NOTE: BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASE FILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION OR DOCUMENTATION OF ABATEMENT OF THIS VIOLATION AS NORMALLY REQUIRED BY 29 CFR 1903.19.
Recent events (3)
- — J (O) $4650
- — C (S) $4500
- — Z (S) $4500
1910.119 E03 III
- Issued
- May 11, 2015
- Abate by
- Jun 5, 2015
- Penalty
- Initial $4,500 · Current $4,650
General-duty citation text
29 CFR 1910.119(e)(3)(iii): The PHA did not address engineering and administrative controls applicable to the hazards and their interrelationships such as appropriate application of safeguards for the hazards identified in the PHA: a) Facility: In the employer's 2013 PHA, the "What If" checklist failed to address the safeguard for the question "What if equipment is nonexistent, inadequate, poorly located or incorrectly used," item 10.11, for the employees who are designated as initial responders for alarm activations or other suspected leaks onsite, on or about 11/17/14. b) Facility: In the employer's 2013 PHA, the What If checklist failed to address the safeguard for he question "What if the PM program for emergency equipment is nonexistent or inadequate," item 10.14. The PHA addressed the fire departments equipment and did not address the equipment needed for the employees involved in onsite emergency response, such as but not limited to full face respirators and personal air monitors, on or about 11/17/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — J (O) $4650
- — C (S) $4500
- — Z (S) $4500
1910.119 H02 II
- Issued
- May 11, 2015
- Abate by
- Jun 5, 2015
- Penalty
- Initial $4,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(h)(2)(ii): The employer did not inform contract employers of potential fire, explosion or toxic release hazards related to working on or near a covered process. a) Facility wide: Spherion and Accu Staffing Services were not informed of the potential for a toxic hazard release of anhydrous ammonia prior to their employees being placed at this location, occurred on or about and times prior thereto 11/17/15. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (S) $0
- — C (S) $4500
- — Z (S) $4500
1910.119 L02 IV
- Issued
- May 11, 2015
- Abate by
- Jun 5, 2015
- Penalty
- Initial $4,500 · Current $4,650
General-duty citation text
29 CFR 1910.119(l)(2)(iv): The written procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affected a covered process did not address the necessary time period for the change: a) Roof: The management of change procedures to replace the pressure relief devices on the oil pots and the high pressure receiver did not address the necessary time period to complete the changes, including, attaching the devices to a common relief header, on or about 11/17/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (O) $4650
- — C (S) $4500
- — Z (S) $4500
1910.119 N
- Issued
- May 11, 2015
- Abate by
- Jun 5, 2015
- Penalty
- Initial $4,500 · Current $4,750
General-duty citation text
29 CFR 1910.119(n): The employer did not establish an emergency plan for the entire plant in accordance with the provisions of 29 CFR 1910.38. In addition, the emergency action plan did not include procedures for handling small releases, nor did it include the hazardous waste and emergency response provisions contained in 29 CFR 1910.120 (a), (p) and (q).: a) Throughout facility: The emergency action plan did not list the specific exit route assignments based on wind direction during an ammonia release as required per 1910.38(c)(2), on or about 11/17/14. b) Throughout facility: The facility did not have a distinctive alarm system for an ammonia release that met the requirements of 1910.165 as required by 1910.38(d), on or about 11/17/14. c)Throughout facility: The employer did not develop an emergency response plan in accordance with the elements listed in section 1910.120(q)(2) of the standard for actions taken during an ammonia release, on or about 11/17/14. d) Throughout facility: Ammonia mechanics required to respond to ammonia leaks to investigate and stop leaks as much as feasibly possible had not received hazardous materials technician training meeting the requirements of the standard in section 120(q)(6)(iii), on or about 11/17/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (S) $4750
- — C (S) $4500
- — Z (S) $4500
1910.119 O01
- Issued
- May 11, 2015
- Abate by
- Jun 5, 2015
- Penalty
- Initial $4,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(o)(1): The employer did not verify that the procedures and practices developed under the standard were being followed: a) Throughout facility: Audits conducted by the employer in 2013 and 2014 to satisfy NJDEP TCPA requirements do not meet OSHA compliance audit specifications for emergency response and emergency action plans for affected employees, on or about 11/17/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (S) $0
- — C (S) $4500
- — Z (S) $4500
1910.151 C
- Issued
- May 11, 2015
- Abate by
- Jun 5, 2015
- Penalty
- Initial $4,500 · Current $4,650
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) Facility, Boiler Room: An eye wash capable of providing 15 minutes of a continuous flow was not provided where employees handle and work with corrosive materials including but not limited to NALCO 7330 and NALCO 73801WR, on or about 11/17/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — J (S) $4650
- — C (S) $4500
- — Z (S) $4500
More inspections at Garelick Farms, LLC
View Garelick Farms, LLC's full OSHA safety record →
More inspections in this industry (NAICS 311511)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340111095.