CAMERON, WV —
OSHA Inspection: WILLIAMS OHIO VALLEY MIDSTREAM LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of WILLIAMS OHIO VALLEY MIDSTREAM LLC in FORT BEELER FACILITY 12681 WAYNESBURG PIKE ROAD, CAMERON, WV 26033 (NAICS 211112). OSHA activity number 338710031.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WILLIAMS OHIO VALLEY MIDSTREAM LLC
- Site address
- FORT BEELER FACILITY 12681 WAYNESBURG PIKE ROAD
- City
- CAMERON
- State
- WV
- ZIP
- 26033
- Mailing
- 100 TELETECH DRIVE SUITE 2, MOUNDSVILLE, WV 26041
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 211112
- Employees
- 42
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.119 D03 II
- Issued
- May 20, 2013
- Abate by
- May 14, 2014
- Penalty
- Initial $4,250 · Current $4,250
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: (a) Fort Beeler Facility, Cameron, WV: The employer did not comply with Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) when it failed to protect employees from fire and explosion hazards inside inadequately protected structures including, but not limited to, the portable lightwood constructed trailer used as the site control room as determined on February 8, 2013. (b) Fort Beeler Facility, Cameron, WV: The employer did not evaluate and document that controls used as safety interlock systems (SIS) such as, but not limited to, PAHH-411A interlock for high pressure in an inlet pre-heater complied with Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) prior to listing this control as a safeguard in the initial Process Hazard Analysis as determined on March 12, 2013. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $4250
- — C (S) $4250
- — Z (S) $4250
1910.119 F01 I D
- Issued
- May 20, 2013
- Abate by
- May 14, 2014
- Penalty
- Initial $4,250 · Current $4,250
General-duty citation text
29 CFR 1910.119(f)(1)(i)(D): The employer did not develop and implement written operating procedures that provide clear instructions for emergency shutdown, including the conditions under which emergency shutdown is required, and the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner: (a) Fort Beeler Facility, Cameron, WV: Written procedures for conducting a manual emergency shutdown of the plant and the conditions requiring a manual emergency shutdown were not developed for operators running the TXP-1, TXP-2, and TXP-3 processes that contain greater than 10,000 pounds of flammable liquids and gases as determined on March 28, 2013. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $4250
- — C (S) $4250
- — Z (S) $4250
More inspections at Williams Ohio Valley Midstream LLC
View Williams Ohio Valley Midstream LLC's full OSHA safety record →
More inspections in this industry (NAICS 211112)
More inspections in WV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338710031.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.