Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WILLIAMS OHIO VALLEY MIDSTREAM LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of WILLIAMS OHIO VALLEY MIDSTREAM LLC in 200 CAIMAN DRIVE, MOUNDSVILLE, WV 26041 (NAICS 211112). OSHA activity number 338738339.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Williams Ohio Valley Midstream LLC — free Get an email when a new federal OSHA severe-injury report for Williams Ohio Valley Midstream LLC is published. One employer, no account, unsubscribe in one click.
Site address
200 CAIMAN DRIVE
City
MOUNDSVILLE
State
WV
ZIP
26041
Mailing
200 CAIMAN DRIVE, MOUNDSVILLE, WV 26041
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
211112
Employees
26
Ownership type
A

2 citations on file for this inspection.

1910.119 D03 II

Other-than-serious 1 instance 12 exposed
Issued
May 20, 2013
Abate by
Jun 21, 2013
Penalty
Initial $4,250 · Current $4,250
29 CFR 1910.119(d)(3)(ii):     The employer did not document that equipment complies with recognized and generally accepted good engineering practices:    (a)  Moundsville Facility:  The employer did not evaluate and document that controls used as safety interlock systems (SIS) such as, but not limited to, PAHH-2000A-F interlock for high pressure complied with Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) prior to listing this control as a safeguard in the initial Process Hazard Analysis as determined on March 27, 2013.    ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — F (O) $4250
  • — C (S) $4250
  • — Z (S) $4250

1910.119 F01 I D

Other-than-serious 1 instance 12 exposed
Issued
May 20, 2013
Abate by
May 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.119(f)(1)(i)(D):     Written operating procedures for emergency shutdown did not include the conditions under which emergency shutdown is required, and the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner:     (a)  Moundsville Facility:  The site written procedures for conducting a manual emergency shutdown of the plant did not include the conditions requiring a manual emergency shutdown for the NGL separation process that contains greater than 10,000 pounds of flammable liquids and gases as determined on March 28, 2013.      ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — F (O) $0
  • — C (S) $0
  • — Z (S) $0

View Williams Ohio Valley Midstream LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338738339.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.