TAMUNING, GU —
OSHA Inspection: BEACH RESORTS, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BEACH RESORTS, LLC in 132 LAGOON DRIVE, TAMUNING, GU 96913 (NAICS 721110). OSHA activity number 338710858.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BEACH RESORTS, LLC
- Site address
- 132 LAGOON DRIVE
- City
- TAMUNING
- State
- GU
- ZIP
- 96913
- Mailing
- 132 LAGOON DRIVE, TAMUNING, GU 96913
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 63
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.303 G01
- Issued
- Mar 27, 2013
- Penalty
- Initial $2,380 · Current $2,380
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Maintenance Shop: On February 7, 2013, and at times prior thereto, a tork timer and eletrical panels 2PNA, 2PNA1, and 2PE, which energized lighting and control panels, were blocked with storage.
Recent events (1)
- — Z (S) $2380
1910.305 B01 II
- Issued
- Mar 27, 2013
- Penalty
- Initial $2,380 · Current $2,380
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On February 7, 2013, and at times prior thereto, and in the following instances, electrical equipment was not properly guarded and live wiring was exposed; A. Kitchen: Electrical panels 2PNK1 and 2PNK2, which energized lighting, were missing blanks. B. Pool Pump Room: An electrical disconnect box, positioned next to panel 2PNP and energized the pool pumps, was missing proper guarding.
Recent events (1)
- — Z (S) $2380
1910.305 B02
- Issued
- Mar 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Kitchen: On February 7, 2013, and at times prior thereto, a two prong outlet cover was missing while energizing two security cameras and the live inner conductors were exposed.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Mar 27, 2013
- Penalty
- Initial $2,380 · Current $2,380
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On February 7, 2013, and at times prior thereto, and in the following instances, extension cords were used in lieu of permanent wiring; A. Kitchen: An orange extension cord was used to energize security cameras and was run through the ceiling. B. Kitchen: An orange and two black extension cords were run through a window and used to energize a hot pot and coffee pot. C. Boiler Room: A black extension cord was used to energize the motor on Boiler 3.
Recent events (1)
- — Z (S) $2380
1910.305 G01 IV B
- Issued
- Mar 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through walls, ceilings, or floors: Kitchen: On February 7, 2013, and at times prior thereto, an orange extension cord was used to energize security cameras and was run through the ceiling.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV C
- Issued
- Mar 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings: Kitchen: On February 7, 2013, and at times prior thereto, an orange and two black extension cords were run through a window and used to energize a hot pot and coffee pots.
Recent events (1)
- — Z (S) $0
1910.334 A02 II
- Issued
- Mar 27, 2013
- Penalty
- Initial $2,380 · Current $2,380
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service: Kitchen: On February 7, 2013, and at times prior thereto, the power cord that energized the rice cooker was damaged, exposing the live inner conductors.
Recent events (1)
- — Z (S) $2380
More inspections at Beach Resorts, LLC
View Beach Resorts, LLC's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in GU
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338710858.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.