FORT MYERS, FL —
OSHA Inspection: SENSIBLE CLOSET COMPANY, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SENSIBLE CLOSET COMPANY, INC. in 5844 ENTERPRISE PKWY, FORT MYERS, FL 33905 (NAICS 321211). OSHA activity number 338738040.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SENSIBLE CLOSET COMPANY, INC.
- Site address
- 5844 ENTERPRISE PKWY
- City
- FORT MYERS
- State
- FL
- ZIP
- 33905
- Mailing
- 5844 ENTERPRISE PKWY, FORT MYERS, FL 33905
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321211
- Employees
- 16
- Ownership type
- A
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Apr 3, 2013
- Abate by
- Apr 29, 2013
- Penalty
- Initial $2,800 · Current $1,960 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to potential fire and explosion hazards associated with the ventilation and collection equipment. For the Sensible Closet Company, Inc. establishment at 5844 Enterprise Parkway, Ft. Myers, FL 33905, as observed on or about 02/06/2013, employees were exposed to fire/explosion hazards associated with: a) A poorly performing and poorly designed ventilation system that failed to capture fugitive dust from machinery such as saws and emitted the dust to the building interior resulting in dust accumulations up to 2-inches deep. The wood dust was analyzed to be a combustible, class II dust. b) Vacuum cleaners used to collect wood dust, which was a combustible, class II dust, were not approved to be used with a class II dust, and accumulations of combustible wood dust were present in their collection bags on a daily basis.
Recent events (2)
- — I (S) $1960
- — Z (S) $2800
1910.22 A01
- Issued
- Apr 3, 2013
- Abate by
- Apr 18, 2013
- Penalty
- Initial $2,800 · Current $1,960 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition. a) For the Sensible Closet facility at 5844 Enterprise Parkway, Ft. Myers, FL 33905, as observed on or about 02/06/2013, employees were exposed to fire/flame-wave and explosion/deflagration hazards associated with the accumulation of combustible wood dust from woodworking equipment on the floor, equipment, duct work overhead, and upper surfaces. The dust was analyzed to be a class II dust with an explosion severity of 0.5700 and a pressure ratio of 6.94. Dust depths were measured from 1/8 in. to over 1 inch deep (including accumulation on electrical equipment), and dust accumulation was measured to cover 24% of the floor surface area.
Recent events (2)
- — I (S) $1960
- — Z (S) $2800
1910.22 A02
- Issued
- Apr 3, 2013
- Abate by
- Apr 18, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.22(a)(2) The floor of every workroom was not maintained in a clean condition. a) For the Sensible Closet facility at 5844 Enterprise Parkway, Ft. Myers, FL 33905, as observed on or about 02/06/2013, employees were exposed to fire/flame-wave and explosion/deflagration hazards associated with the accumulation of combustible wood dust from woodworking equipment on the floor, equipment, duct work overhead, and upper surfaces. The dust was analyzed to be a class II dust with an explosion severity of 0.5700 and a pressure ratio of 6.94. Dust depths were measured from 1/8 in. to over 1 inch deep (including accumulation on electrical equipment), and dust accumulation was measured to cover 24% of the floor surface area.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.307 C
- Issued
- Apr 3, 2013
- Abate by
- Apr 13, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) For the Sensible Closet facility at 5844 Enterprise Parkway, Ft. Myers, FL 33905, as observed on or about 02/06/2013, employees were exposed to fire/flame-wave and explosion/deflagration hazards associated with the accumulation of combustible wood dust from woodworking equipment on the floor, equipment, duct work overhead, and upper surfaces. The dust was analyzed to be a class II dust with an explosion severity of 0.5700 and a pressure ratio of 6.94. Dust depths were measured from 1/8 in. to over 1 inch deep (including accumulation on electrical equipment), and dust accumulation was measured to cover 24% of the floor surface area. Combustible wood dust was accumulated on electrical equipment including, but not limited to, electrical transformers, switches, and breaker boxes. Dust was accumulated on electrical equipment at depths of inch. and over.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.38 A
- Issued
- Apr 3, 2013
- Abate by
- Apr 22, 2013
- Penalty
- Initial $1,600 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.38(a)(1): The emergency action plan required by 29 CFR 1910.157(a) or (b) when the employer has elected to partially or totally evacuate the workplace in the event of a fire emergency, or required by 29 CFR 1910.160(c)(1), did not cover the designated actions that the employer or employees must take to ensure employee safety from the fire and other emergencies: a) For the Sensible Closet facility at 5844 Enterprise Parkway, Ft. Myers, FL 33905, as observed on or about 02/06/2013, employees were not aware of their responsibilities under the emergency action plan including, but not limited to, their requirement to fight fires or to totally evacuate.
Recent events (2)
- — I (S) $1120
- — Z (S) $1600
More inspections at Sensible Closet Company, INC.
View Sensible Closet Company, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 321211)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338738040.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.