Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,192,068Inspections Most recent open 2026-08-04 Last loaded 2026-08-07

OSHA Inspection: TSUDIS CHOCOLATE CO., INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TSUDIS CHOCOLATE CO., INC. in 610 ALPHA DRIVE, PITTSBURGH, PA 15238 (NAICS 311320). OSHA activity number 338822638.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tsudis Chocolate CO., INC. for free Get an email when a new federal OSHA severe-injury report for Tsudis Chocolate CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
610 ALPHA DRIVE
City
PITTSBURGH
State
PA
ZIP
15238
Mailing
610 ALPHA DRIVE, PITTSBURGH, PA 15238
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311320
Employees
195
Ownership type
A

21 citations on file for this inspection.

1910.147 C04 II

Serious Gravity 10 3 instances 5 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $6,930 · Current $5,544 Reduced
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D):    (a) Facility, Sheeting Line Two: On or before February 11, 2013, the employer did not create an energy control procedure that specifically addressed setting up the equipment for a production cycle. The procedure did not list all energy sources and lock out points that would be necessary to control the roll and belt movement. An employee was injured while installing the product guide rails.     (b) Facility, Sheeting Line Two: On or before February 14, 2013, the employer did not create an energy control procedure that specifically identified setting up the equipment for a production cycle. The procedure did not list all energy sources and lock out points that would be necessary to control the roll and belt movement. Employees were exposed while installing the product guide rails.      (c) Facility, Sheeting Line Two: On or before February 14, 2013, the employer did not create an energy control procedure that specifically identified repair work being completed on an elevated roll. The second sizing roll procedure did not list controls for belt movement or gravitational potential energy.
Recent events (2)
  • · I (S) $5544
  • · Z (S) $6930

1910.147 C06 I

Serious Gravity 5 1 instance 6 exposed
Issued
Aug 7, 2013
Abate by
Sep 30, 2013
Penalty
Initial $3,960 · Current $3,168 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:     (a) Facility: On or about February 14, 2013, the employer utilizes procedures for the control of hazardous energy and did not conduct a periodic inspection of those procedures at least annually.
Recent events (2)
  • · I (S) $3168
  • · Z (S) $3960

1910.147 C07 I A

Serious Gravity 10 2 instances 5 exposed
Issued
Aug 7, 2013
Abate by
Sep 30, 2013
Penalty
Initial $6,930 · Current $5,544 Reduced
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation:     (a) Facility, Sheeting Line Two: On or before February 11, 2013, the employer did not provide training to employees to recognize that set-up activities expose them to hazardous energy.                (b) Facility, Sheeting Line Two: On or before February 14, 2013, the employer did not provide training to employees to recognize that set-up activities expose them to hazardous energy.
Recent events (2)
  • · I (S) $5544
  • · Z (S) $6930

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 7, 2013
Penalty
Initial $3,960 · Current $3,168 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:     (a) Maintenance Shop, Wilton Vertical Belt and Round Disk Sander:  On or before February 13, 2013, An employee used a Wilton vertical and round disk sander to grind on a piece of metal.  The vertical belt was missing its guard exposing the employee to the in running nip point.
Recent events (2)
  • · I (S) $3168
  • · Z (S) $3960

1910.303 G02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 7, 2013
Penalty
Initial $4,950 · Current $3,960 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):     (a) Chocolate Holding/Dispensing Tank, Line Number Two: On or before February 14, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a cover was not affixed to prevent exposure to live electrical parts.
Recent events (2)
  • · I (S) $3960
  • · Z (S) $4950

1910.219 F03

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven feet or less above floors or platforms were not enclosed:    (a) Facility, Sheeting Line Two, Chocolate Holding/Dispensing Tank: On or before February 14, 2013, an employee, attempting to secure a loose conduit located beneath the chocolate holding/dispensing tank, was exposed to a rotating chain and sprocket.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 3 instances 8 exposed
Issued
Aug 7, 2013
Abate by
Aug 26, 2013
Penalty
Initial $3,960 · Current $3,168 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:     (a) Chocolate Holding/Dispensing Unit, Line Number Two: On or before February 14, 2013, employees were exposed to electrical shock and/or arcing part hazards in that a flexible metallic conduit connector was used in lieu of flexible cord connector. The cord was found pulling away from the connector.         (b) Electrical Receptacle, Line Number One: On or before February 14, 2013, employees were exposed to electrical shock and/or arcing part hazards in that a utility box and receptacle were subjected to water from cleaning activities and not designed for use in such an environment.        (c) Facility, Wrapping and Packing Area: On or before February 14, 2013, employees were exposed to fire hazards in that a plug strip was being used in a manufacturing environment.
Recent events (2)
  • · I (S) $3168
  • · Z (S) $3960

1910.303 B07 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $3,960 · Current $3,168 Reduced
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:      (a) Facility, Packaging Area: On or before February 14, 2013, a flexible cord used to power a conveyor was damaged due to the belt slicing the cord.
Recent events (2)
  • · I (S) $3168
  • · Z (S) $3960

1910.304 G05

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 7, 2013
Penalty
Initial $4,950 · Current $3,960 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:      (a) Chocolate Holding/Dispensing Tank, Line Number Two: On or before February 14, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a metallic conduit was separated from the tank without a separate grounding conductor contained within the raceway.
Recent events (2)
  • · I (S) $3960
  • · Z (S) $4950

1910.305 B01 III C

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(iii)(C): A fitting was not provided on each end of the raceway to protect the cable from abrasion, and the fittings remain accessible after installation:   (a) Chocolate Holding/Dispensing Tank, Line Number Two: On or before February 14, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a metallic conduit was not equipped with a protective bushing at its attachment point.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B01 III F

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(iii)(F): The raceway was not fastened at its outer end and at other points as necessary:    (a) Chocolate Holding/Dispensing Tank, Line Number Two: On or before February 14, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that a metallic conduit was not attached.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 2 instances 5 exposed
Issued
Aug 7, 2013
Abate by
Aug 26, 2013
Penalty
Initial $3,960 · Current $3,168 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:     (a) Facility, Sheeting Line Two, Chocolate Holding/Dispensing Tank: On or before February 14, 2013, the employer used a flexible cord to power the equipment.         (b) Facility, Wrapping and Packing Area: On or before February 14, 2013, the employer used a flexible cord to power a conveyor.
Recent events (2)
  • · I (S) $3168
  • · Z (S) $3960

1910.305 G02 III

Serious Gravity 5 3 instances 5 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $3,960 · Current $3,168 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:     (a) Chocolate Holding/Dispensing Tank, Line Number Two: On or before February 14, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that conductors were pulling out of a connector placing strain on its connections.        (b) Facility, Wrapping and Packing Area: On or before February 14, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that conductors were pulling out of a connector placing strain on its connections.     (c) Facility, Wrapping and Packing Area: On or before February 14, 2013, employees were exposed to electrical shock, arcing parts, and/or fire hazards in that conductors were pulling out of an attachment plug placing strain on its connections.
Recent events (2)
  • · I (S) $3168
  • · Z (S) $3960

1910.332 B01

Serious Gravity 10 1 instance 4 exposed
Issued
Aug 7, 2013
Abate by
Aug 26, 2013
Penalty
Initial $6,930 · Current $5,544 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:     (a) Facility, On or about February 11, 2013, employees who perform electrical repairs and/or maintenance were not trained in that they were not familiar with the necessary PPE requirements, circuit testing techniques, and/or de-energizing requirements.
Recent events (2)
  • · I (S) $5544
  • · Z (S) $6930

1910.333 A01

Serious Gravity 5 2 instances 2 exposed
Issued
Aug 7, 2013
Penalty
Initial $4,950 · Current $0 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:       (a) Facility, Molding Line Two: On or Before February 15, 2013, an employee was exposed to 120 Volts AC while re-seating a fuse in its holder. The employee did not conduct a voltage test to verify electrical isolation.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4950

1910.212 A03 II

Repeat Gravity 10 4 instances 7 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $13,860 · Current $11,088 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):           (a) Kitchen Area, First Sizing Roll, Sheeting Line Two: On or before February 8, 2013, employees were exposed to in running nip points while patching in product on the sheeting line.           (b) Kitchen Area, Second Sizing Roll, Sheeting Line Two: On or before February 8, 2013, employees were exposed to in running nip points while patching in product on the sheeting line.           (c) Kitchen Area, Hobart Mixer: On or before February 14, 2013, an employee was exposed to struck-by and/or caught by hazards in that a mixing paddle was not guarded.         (d) Facility, Sheeting Line Two, Chocolate Holding/Dispensing Tank: On or before February 14, 2013, employees were exposed to a rotating paddle when adding chocolate to the holding/dispensing tank.       The Tsudis Chocolate Company, Inc., was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.212(a)(3)(ii), which was contained in OSHA inspection number 315562058, citation number 1, item number 5, and was affirmed as a final order on 4/17/2012, with respect to a workplace located at 610 Alpha Drive, Pittsburgh, PA 15238.
Recent events (2)
  • · I (R) $11088
  • · Z (R) $13860

1910.335 A01 I

Repeat Gravity 10 1 instance 5 exposed
Issued
Aug 7, 2013
Abate by
Aug 26, 2013
Penalty
Initial $13,860 · Current $10,080 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:     (a) Facility, On or about February 11, 2013, employees have worked on energized electrical parts and they do not have rubber insulating gloves for use when trouble shooting equipment up to and including 480 Volts AC Three-Phase.      The Tsudis Chocolate Company, Inc., was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.335(a)(1)(i), which was contained in OSHA inspection number 315562058, citation number 1, item number 13, and was affirmed as a final order on 4/17/2012, with respect to a workplace located at 610 Alpha Drive, Pittsburgh, PA 15238.
Recent events (2)
  • · I (R) $10080
  • · Z (R) $13860

1910.147 C05 II D

Other-than-serious 1 instance 1 exposed
Issued
Aug 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(5)(ii)(D): Lockout devices and tagout devices did not indicate the identity of the employee applying the device(s):   (a) Kitchen Area, Slab Forming Line Number Two: On or before February 14, 2013, a maintenance technician did not disclose their identity on a lock used to isolate a roll drive motor.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.212 B

Deleted Other-than-serious 1 instance 1 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:   (a) Kitchen Area, Hobart Mixer: On or before February 14, 2013, employees were exposed to struck-by hazards in that the mixer was not secured and leveled on a solid surface during its operating cycles.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.303 G01

Other-than-serious 1 instance 1 exposed
Issued
Aug 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:   (a) Kitchen Area, Molding Line Number One: On or before February 14, 2013, ingredient bins were being stored in front of the MCC (Motor Control Center).
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 E01

Other-than-serious 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Sep 30, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panel board enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:      (a) Facility, Sheeting Line One, Electrical Receptacle/Box: On or before February 11, 2013, an electrical receptacle mounted in a metal utility box on a wall adjacent to sheeting line one, which is cleaned using a water hose, potentially exposes employees to an electrical hazard.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Tsudis Chocolate CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338822638.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.