BRISTOL, CT —
OSHA Inspection: BRISTOL CROSSING, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BRISTOL CROSSING, LLC in 61 BELLEVUE AVENUE, BRISTOL, CT 06010 (NAICS 623110). OSHA activity number 338953920.
Where did this inspection happen?
- Establishment
- BRISTOL CROSSING, LLC
- Site address
- 61 BELLEVUE AVENUE
- City
- BRISTOL
- State
- CT
- ZIP
- 06010
- Mailing
- 61 BELLEVUE AVENUE, BRISTOL, CT 06010
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623110
- Employees
- 200
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.37 A04
- Issued
- Jun 12, 2013
- Abate by
- Jul 30, 2013
- Penalty
- Initial $3,600 · Current $1,800 Reduced
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: On or about March 12, 2013, the Emergency Exit near the Old Compressor Room: The self-closer on the right-side emergency exit door was broken. The door was locked with head and foot bolts.
Recent events (2)
- — I (S) $1800
- — Z (S) $3600
1910.212 A01
- Issued
- Jun 12, 2013
- Abate by
- Jun 12, 2013
- Penalty
- Initial $4,500 · Current $2,250 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about March 12, 2013, the Vertipac Compactor was not provided with a positive pressure switch or an interlock.
Recent events (2)
- — I (S) $2250
- — Z (S) $4500
1910.303 G01 II
- Issued
- Jun 12, 2013
- Abate by
- Jun 12, 2013
- Penalty
- Initial $3,060 · Current $1,530 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: On or about March 12, 2013, the required working space about electrical equipment was used for storage: A. Old Compressor Room: The 220V freezer disconnect and the 100V cooler disconnect were blocked by the storage of stackable metal chairs. B. Central Supply, LL6: Panel AH-B1 and B2 was blocked by the placement of an office desk. C. Basement Electrical Room: Panel EP-S was blocked by the placement of a dolly and electrical lugs. D. Sub-Basement Storage Room: Eaton Panelboard DP-1 was blocked by the storage of construction materials.
Recent events (2)
- — I (S) $1530
- — Z (S) $3060
1910.303 G02 I
- Issued
- Jun 12, 2013
- Abate by
- Jun 12, 2013
- Penalty
- Initial $3,600 · Current $1,800 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): On or about March 12, 2013, in the following locations, employees were exposed to electric shocks: A. First Floor, Old Compressor Room: A Paragon timer box did not have the inner conductors guarded. B. Sub-Basement Storage Room: The trim plate on the 120/208Y Eaton Panel DP-1 was not securely installed.
Recent events (2)
- — I (S) $1800
- — Z (S) $3600
1910.304 G05
- Issued
- Jun 12, 2013
- Abate by
- Jun 12, 2013
- Penalty
- Initial $5,400 · Current $2,700 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about March 12, 2013, employees were exposed to electric shock hazards in the following locations: A. Laundry, LL12: An Air King metal encased fan for area cooling, was missing a ground pin. B. Janitor's Closet, LL9: Tornado high speed floor burnisher was missing a ground pin. C. Beauty Salon, LL7: Collins Hot Spot Hair Dryer, #183 was missing a ground pin.
Recent events (2)
- — I (S) $2700
- — Z (S) $5400
1910.305 G01 IV A
- Issued
- Jun 12, 2013
- Abate by
- Jun 12, 2013
- Penalty
- Initial $3,060 · Current $1,530 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about March 12, 2013, Kitchen, LL21: Two Coleman/CCI 600V bus drop cables were used in lieu of fixed wiring to power a Lakeside plate warmer and a Vollrath steam table.
Recent events (2)
- — I (S) $1530
- — Z (S) $3060
1910.305 G01 IV B
- Issued
- Jun 12, 2013
- Abate by
- Jun 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors: On or about March 12, 2013, Kitchen, LL21: Two Coleman/CCI 600V bus drop cables were run through holes in ceiling tiles to power a Lakeside plate warmer and a Vollrath steam table.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1904.32 B03
- Issued
- Jun 12, 2013
- Abate by
- Jul 30, 2013
- Penalty
- Initial $900 · Current $450 Reduced
General-duty citation text
29 CFR 1904.32(b)(3): A company executive did not certify the he or she had examined the OSHA 300 Log and that he or she reasonably believed, based on his or her knowledge of the process by which the information was recorded, that the annual summary was correct and complete: On or about March 12, 2013, in Break Room, LL3: The OSHA 300A Summary of Work Related Injuries and Illnesses for 2012, which was posted for review, was not signed by the highest person in management at the facility.
Recent events (2)
- — I (O) $450
- — Z (O) $900
1910.37 A03
- Issued
- Jun 12, 2013
- Abate by
- Jun 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: On or about March 12, 2013, Basement Electrical Room: The side-hinged exit door was unable to open fully due to the placement of a storage cabinet in the exit route.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Bristol Crossing, LLC
View Bristol Crossing, LLC's full OSHA safety record →
More inspections in this industry (NAICS 623110)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338953920.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.