Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: COMBINED SYSTEMS INC - PENN ARMS DIVISION

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of COMBINED SYSTEMS INC - PENN ARMS DIVISION in 107 PINE STREET, PUNXSUTAWNEY, PA 15767 (NAICS 332994). OSHA activity number 338990021.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Combined Systems INC - Penn Arms Division for free Get an email when a new federal OSHA severe-injury report for Combined Systems INC - Penn Arms Division is published. One employer, no account, unsubscribe in one click.
Site address
107 PINE STREET
City
PUNXSUTAWNEY
State
PA
ZIP
15767
Mailing
107 PINE STREET, PUNXSUTAWNEY, PA 15767
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332994
Employees
22
Ownership type
Private (A)

2 citations on file for this inspection.

1910.107 D03

Serious Gravity 5 1 instance 20 exposed
Issued
Sep 12, 2013
Abate by
Oct 30, 2013
Penalty
Initial $4,000 · Current $3,000 Reduced
29 CFR 1910.107(d)(3): The spray booth did not have an independent exhaust duct system discharging to the exterior of the building.   a.) Paint Room - employee(s) performed air spraying of Wurdack 13209 Matte Black paint which contains up to 10% n-butoxyethanol in the spray booth which was equipped with an exhaust fan that did not discharge exhausted air to the outside of the building.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $4000

1910.307 C

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 12, 2013
Abate by
Oct 30, 2013
Penalty
Initial $5,000 · Current $3,750 Reduced
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:    a.) Paint Room - Employees conducting spraying operations in the paint room were potentially exposed to fire and explosion hazards in that non-explosion proof electrical equipment including, but not limited to, fluorescent lights, fans, electrical outlets, and flexible cords was present inside the paint room.
Recent events (2)
  • · I (S) $3750
  • · Z (S) $5000

View Combined Systems INC - Penn Arms Division's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338990021.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.