MACUNGIE, PA —
OSHA Inspection: LEOTAUR TECHNOLOGY GROUP, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LEOTAUR TECHNOLOGY GROUP, INC. in 111 LEHIGH STREET, MACUNGIE, PA 18062 (NAICS 326191). OSHA activity number 339007726.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LEOTAUR TECHNOLOGY GROUP, INC.
- Site address
- 111 LEHIGH STREET
- City
- MACUNGIE
- State
- PA
- ZIP
- 18062
- Mailing
- 111 LEHIGH STREET, MACUNGIE, PA 18062
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326191
- Employees
- 20
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.37 A03
- Issued
- May 15, 2013
- Abate by
- May 15, 2013
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) West Side Of Building - An exit route was obstructed with pallets and material to a width of 24 inches, on or about 2/6/13. b) Rear Of Building - An exit door was blocked with a table and other materials, on or about 2/6/13.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.147 C01
- Issued
- May 15, 2013
- Abate by
- Jun 4, 2013
- Penalty
- Initial $2,000 · Current $1,200 Reduced
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: (a) Throughout Facility - Employees are conducting maintenance on energized pieces of equipment, including but not limited to grinders, polishers, casting machines and granite cutters, without the protection of a hazardous energy control program, on or about 2/6/13.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
1910.151 C
- Issued
- May 15, 2013
- Abate by
- Jun 19, 2013
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) Adjacent to the spray booth - employees are servicing forklift batteries, containing corrosive liquids, and did not have an available eyewash for the expedient flushing of their eyes, on or about 2/6/13.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.242 B
- Issued
- May 15, 2013
- Abate by
- Jun 19, 2013
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: a) Custom Set Up Area - employees were using unregulated compressed air for cleaning that was measured at 40 p.s.i., on or about 2/6/13.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.303 G01 II
- Issued
- May 15, 2013
- Abate by
- May 15, 2013
- Penalty
- Initial $1,700 · Current $1,020 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: (a) Rear Of Building - The electrical panel box that supplies power to the building was blocked with excess pallets and wood pieces, on or about 2/6/13.
Recent events (2)
- — I (S) $1020
- — Z (S) $1700
1910.22 A01
- Issued
- May 15, 2013
- Abate by
- May 25, 2013
- Penalty
- Initial $0 · Current $0
2280
General-duty citation text
29 CFR 1910.22(a)(1): Place(s) of employment were not kept clean and orderly, or in a sanitary condition: a) Adjacent to dust collector - employees are working near the dust collection system which is not sufficiently capturing large quantities of dusty grinding residue and creating a slipping hazard, on or about 1/31/13.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.178 L04 I
- Issued
- May 15, 2013
- Abate by
- Jun 19, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(4)(i): 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance shall be conducted at least once every three years: a) Throughout Facility - The operators of the powered industrial truck have not had training since 2006 on or about 2/6/13.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Leotaur Technology Group, INC.
View Leotaur Technology Group, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 326191)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339007726.