TAMUNING, GU —
OSHA Inspection: FAMILIA SUSIM CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FAMILIA SUSIM CORPORATION in 1991 ARMY DRIVE, TAMUNING, GU 96913 (NAICS 493110). OSHA activity number 339008484.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FAMILIA SUSIM CORPORATION
- Site address
- 1991 ARMY DRIVE
- City
- TAMUNING
- State
- GU
- ZIP
- 96913
- Mailing
- 1991 ARMY DRIVE, RUELOS BUILDING, TAMUNING, GU 96913
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 4
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.37 B05
- Issued
- Jul 8, 2013
- Abate by
- Jul 18, 2013
- Penalty
- Initial $1,200 · Current $900 Reduced
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet). Main Storage, back door south side: On April 12, 2013, the back door was not an exit and could be mistaken as an exit therefore must be marked as NOT an EXIT.
Recent events (2)
- — I (S) $900
- — Z (S) $1200
1910.37 B06
- Issued
- Jul 8, 2013
- Abate by
- Jul 18, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m2) are permitted. Main Storage, north exit door: On April 12, 2013, the single exit door at the end of the hallway, the EXIT sign was not illuminated and endangering workers in the event of an emergency.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 E03
- Issued
- Jul 8, 2013
- Abate by
- Jul 18, 2013
- Penalty
- Initial $1,200 · Current $900 Reduced
General-duty citation text
29 CFR 1910.157(e)(3): The date of the annual maintenance check of portable fire extinguishers was not recorded: Main Storage Room: On April 12, 2013, the fire extinguisher onsite had not received annual maintenance inspection/service. The tag normally hang on the fire extinguisher was missing and no record of inspection was available.
Recent events (2)
- — I (S) $900
- — Z (S) $1200
1910.157 G01
- Issued
- Jul 8, 2013
- Abate by
- Aug 1, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting: This violation was discovered on April 12, 2013 at the Forex building; where an educational program was not provided for employees to familiarize them with the general principles of fire extinguisher use and the hazards and employees were expected to use fire extinguishers in the event of a fire.