Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FLOWERS BAKING CO. OF BRADENTON, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FLOWERS BAKING CO. OF BRADENTON, LLC in 6490 PARKLAND DR., BRADENTON, FL 34212 (NAICS 311812). OSHA activity number 339032229.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Flowers Baking CO. of Bradenton, LLC — free Get an email when a new federal OSHA severe-injury report for Flowers Baking CO. of Bradenton, LLC is published. One employer, no account, unsubscribe in one click.
Site address
6490 PARKLAND DR.
City
BRADENTON
State
FL
ZIP
34212
Mailing
P.O. BOX 20539, BRADENTON, FL 34204
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311812
Employees
190
Ownership type
A

3 citations on file for this inspection.

1910.303 B07 IV

Serious Gravity 10 1 instance 5 exposed
Issued
Aug 1, 2013
Penalty
Initial $6,300 · Current $4,000 Reduced
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemcial action or overheating.      A)As observed on or about 04/30/2013, the energy isolating device of the dough chunker machine was broken and not capable of being locked out in off position.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $6300

1910.303 F01

Serious Gravity 10 1 instance 6 exposed
Issued
Aug 1, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  (a) As observed on or about 04/30/2013, the disconnecting device of the Sponge Mixer control panel was not identified.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Deleted Serious Gravity 10 1 instance 6 exposed
Issued
Aug 1, 2013
Abate by
Sep 18, 2013
Penalty
Initial $6,300 · Current $0 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  (a) As observed on or about 04/30/2013, maintenance employees routinely service electrical machinery while energized at voltages that range from 120 to 460 volts are exposed to electric shocks, arc flash and arc blast hazards. The employees are provided with 00 electrical gloves, cotton shirts and non-electrical rated faceshields as personal protective equipment to mitigate the hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6300

View Flowers Baking CO. of Bradenton, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339032229.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.