PITTSBURGH, PA ·
OSHA Inspection: NEVILLE CHEMICAL COMPANY
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of NEVILLE CHEMICAL COMPANY in 2800 NEVILLE ROAD, PITTSBURGH, PA 15225 (NAICS 325211). OSHA activity number 339073991.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEVILLE CHEMICAL COMPANY
- Site address
- 2800 NEVILLE ROAD
- City
- PITTSBURGH
- State
- PA
- ZIP
- 15225
- Mailing
- 2800 NEVILLE ROAD, PITTSBURGH, PA 15225
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325211
- Employees
- 180
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
1910.119 D03 II
- Issued
- Oct 25, 2013
- Abate by
- Aug 31, 2014
- Penalty
- Initial $4,500 · Current $2,800 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: a) In the facility, on or about October 21, 2013 - Where the Unit 20 Shell and Tube Reactor was provided with overpressure protection by system design in lieu of a pressure relief device, the employer did not document that the equipment complied with RAGAGEP, such as ASME Boiler & Pressure Vessel Code Section VIII Code Case 2211 for overpressure protection by system design. b) In the facility, on or about October 21, 2013 - Where the Unit 21 East Spiral Reactor was provided with overpressure protection by system design in lieu of a pressure relief device, the employer did not document that the equipment complied with RAGAGEP, such as ASME Boiler & Pressure Vessel Code Section VIII Code Case 2211 for overpressure protection by system design.
Recent events (2)
- · I (S) $2800
- · Z (S) $4500
More inspections at Neville Chemical Company
View Neville Chemical Company's full OSHA safety record →
More inspections in this industry (NAICS 325211)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339073991.